Modesto, CA Fire Regulations: Smoke Detectors (2026)
Key Facts
- Required occupancies
- Groups R-2, R-3, R-4 and unregulated dwellings
- Placement
- Outside sleeping areas, in bedrooms, every story
- Power source
- Building wiring plus battery backup
- Interconnection
- One alarm activates all alarms in the unit
- Battery-only exception
- No commercial power or no construction underway
- Code source
- Ord. 3513-C.S., eff. 6-12-09
Summary
Modesto requires interconnected, hardwired smoke alarms with battery backup in every sleeping area, sleeping room and story of Group R dwellings, under the fire safety article of its Property Maintenance Code.
Single or multiple-station smoke alarms shall be installed and maintained in Groups R-2, R-3, R-4 and in dwellings not regulated in Group R occupancies, regardless of occupant load at all of the following locations: (a)On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms.(b)In each room used for sleeping purposes.(c)In each story within a dwelling unit, including basements and cellars but not including crawl spaces and uninhabitable attics.
Official source re-checked September 7, 2026: no newer edition of the code had been published (publisher’s edition: Code of Ordinances: Supplement 71).
Full Breakdown
2710 requires single or multiple-station smoke alarms in Groups R-2, R-3, R-4 and in other dwellings not regulated as Group R occupancies, regardless of occupant load. Alarms are required on the ceiling or wall outside each separate sleeping area in the immediate vicinity of bedrooms, inside each room used for sleeping, and on each story of the dwelling unit including basements and cellars (crawl spaces and uninhabitable attics are excluded). For split-level units without a door between adjacent levels, a single alarm on the upper level covers the lower level if that lower level sits less than one full story below.
2711 governs the power source: alarms in Group R occupancies must draw primary power from building wiring served by a commercial source, backed up by battery, and must emit a low-battery signal; the wiring must be permanent with no disconnect switch other than required overcurrent protection. A battery-only alarm is permitted where no construction is underway, where the building has no commercial power source, or during alterations that do not expose the structure by removing interior wall or ceiling finishes, unless an accessible attic, crawl space or basement would allow wiring without removing those finishes.
2712 requires interconnection: where more than one alarm is required within a dwelling unit in Groups R-2, R-3, R-4 and unregulated dwellings, all alarms must be wired so that one activating sets off every alarm in the unit, audible in every bedroom over background noise with doors closed. Interconnection is not required in buildings undergoing no alterations, repairs or construction, or where existing-area work does not expose the structure.
Violations & Fines
A dwelling missing a required smoke alarm location, running battery-only power where hardwiring is required, or lacking interconnection where the code demands it is a Property Maintenance Code deficiency enforceable through Modesto Code Enforcement's standard correction and inspection-fee process under Title 9.
Frequently Asked Questions
Does a Modesto rental need a smoke alarm in every bedroom?
Can smoke alarms in a Modesto rental run on batteries only?
Do all the smoke alarms in a unit have to go off together?