Kings County, CA Data Centers & Crypto Mining: Data Center Noise Limits (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified July 2026

Key Facts

Daytime Limit
55 dBA Leq (7am-10pm)
Nighttime Limit
50 dBA Leq (10pm-7am)
Max Level (Lmax)
75 day / 70 night
Governing Doc
General Plan Noise Element
Tonal/Impulsive Penalty
Minus 5 dB

Summary

Kings County's 2035 General Plan Noise Element caps stationary (non-transportation) noise at a home at 55 dBA daytime and 50 dBA at night (Leq), with maximum levels of 75 and 70 dBA. A data center's cooling and generators must meet these limits through a required acoustical analysis.

These county ordinances apply to unincorporated areas of Kings County. Incorporated cities within the county may have their own rules that take precedence over county-level regulations.

Appropriate noise mitigation measures shall be included in a proposed project design when the proposed new use(s) will be affected by or include non-transportation noise sources and exceed the County's "Non-Transportation Noise Standards" (Table N-8).

Source: Kings County Development Code (Art. 8, Industrial Zoning Districts) & 2035 General Plan Noise ElementView official code

Full Breakdown

Kings County's numeric noise standards live in the 2035 General Plan Noise Element, not a standalone decibel ordinance (County Code Chapter 15, Article X handles nuisance noise separately). A data center's chillers, cooling fans, and backup generators are non-transportation noise sources. Under Table N-8, applied at the receiving use, noise at a home may not exceed an average (Leq) of 55 dBA daytime (7 a.m.-10 p.m.) and 50 dBA nighttime (10 p.m.-7 a.m.), with maximum (Lmax) levels of 75 and 70 dBA. Tonal, impulsive, or speech-like sounds get an extra 5 dB penalty. Policy B1.1.1 requires a project to mitigate to compliance. Generators run during power outages are exempt, and routine testing is exempt in daytime under one hour weekly.

Violations & Fines

Cooling or generator noise above 55 dBA Leq by day or 50 dBA at night at a nearby home fails the Noise Element standards, blocks permit approval, and triggers required mitigation before the project can proceed.

Frequently Asked Questions

How loud can a Kings County data center be?
No more than 55 dBA (Leq) during the day and 50 dBA at night at a nearby home, under the General Plan Noise Element's Table N-8. Tonal or pulsing noise is held five decibels lower.
Are data center backup generators covered for noise?
Generators must meet the 55/50 dBA limits in normal use, but generators activated during power outages are exempt, and routine testing is exempt if it occurs in daytime and under one hour per week.

Sources & Official References

Other rules in Kings County

All Kings County rules

California rules heatmap·Compare Kings County to another location·View the California data centers & crypto mining overview

Get notified when Data Center Noise Limits in Kings County, CA changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Data Center Noise Limits in Cities Across Kings County