Propane (LP-gas) and petroleum storage in unincorporated Sonoma County is regulated through the California Fire Code adopted in County Code Chapter 13 and Permit Sonoma's hazardous-materials program. LP-gas installations require a Fire Code permit before filling, and aboveground petroleum facilities of 1,320 gallons or more must maintain a federal SPCC plan under the Aboveground Petroleum Storage Act.
Sonoma County regulates fuel storage through two channels. First, the California Fire Code - adopted with local amendments in Chapter 13 of the Sonoma County Code - governs liquefied petroleum gas (LP-gas/propane). Under California Fire Code Chapter 61, a permit is required for LP-gas installations, and a distributor may not fill an LP-gas container for which a permit is required unless an installation permit has been issued for that location by the fire code official. Where a single LP-gas container exceeds 2,000 gallons water capacity, or aggregate capacity exceeds 4,000 gallons, the installer must submit construction documents, and LP-gas equipment must be installed in accordance with the California Mechanical Code and NFPA 58.
Second, Permit Sonoma's Fire Prevention and Hazardous Materials Division administers the aboveground petroleum storage program. Owners and operators of aboveground petroleum storage tanks must obtain permit approval prior to installation, may need to file a Hazardous Materials Business Plan, and 'must develop and maintain' a Spill Prevention, Control, and Countermeasure (SPCC) plan if the facility has 'aboveground storage capacity of 1,320 gallons or greater' under the Aboveground Petroleum Storage Act (APSA) of 1990, following 40 CFR Part 112.
For typical residential propane tanks, the practical requirement is correct installation, fire-code clearances, and a permit through the fire code official; larger commercial or agricultural installations trigger the construction-document and hazardous-materials-plan thresholds described above.
Installing or filling a regulated LP-gas container without the required Fire Code permit, or operating an aboveground petroleum facility of 1,320 gallons or more without an SPCC plan, violates the adopted California Fire Code and APSA. Contact Permit Sonoma Hazardous Materials at (707) 565-2024 before installation.
Other ordinances people look up for this city. Green dot = verified primary-source excerpt.
Sonoma County, CA
Outdoor music, concerts and special events in unincorporated Sonoma County are regulated through the use-permit and special-event review process rather than ...
Sonoma County, CA
Sonoma County has no enforceable countywide decibel ordinance for everyday noise. The General Plan Noise Element Table NE-2 sets exterior performance standar...
Sonoma County, CA
On County roads in unincorporated Sonoma County, loading and passenger-loading zones are established under Sonoma County Code Sec. 18-3.3 and marked by curb ...
Sonoma County, CA
Sonoma County Code Sec. 18-3.10 prohibits parking any 'oversized vehicle' on a County road or right-of-way for more than six consecutive hours, after which i...
Sonoma County, CA
Fences in unincorporated Sonoma County must meet zoning height limits by yard, sit at least 6 inches outside public rights-of-way and easements, and be measu...
Sonoma County, CA
Residential and K-district fences in unincorporated Sonoma County may use wood, naturalistic composite wood, stone or masonry, stucco/plaster, woven metal or...
See how Sonoma County's propane storage rules stack up against other locations.
Help us keep this page accurate. If you notice an error or outdated information, let us know.