Maui County, HI Building Safety: Fire Sprinkler Requirements (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified October 2026

Key Facts

Class A (no fire protection)
At least 100 feet from other structures and property lines
Class B requirement
Automatic fire sprinkler system plus an electrical permit
Design standard
NFPA 13, with a hale-specific alternative in 405.2
Flow per head
18 gpm for the first head, 13 gpm for each additional
Water pressure
40 psi at the riser base, 12 psi at the highest sprinkler
Water supply duration
30 minutes, certified by an engineer or C-20 contractor
Sleeping hale
Approved battery-operated smoke alarm required

Summary

Maui County Code § 16.25.405 sorts Indigenous Hawaiian architecture structures (hale) into two fire protection classes by setback. Class A hale sit at least 100 feet from every other structure and every property line and need no fire protection. Class B hale meet zoning setbacks but miss that 100-foot test, so they must have an automatic fire sprinkler system, and an electrical permit is required for it.

These county ordinances apply to unincorporated areas of Maui County. Incorporated cities within the county may have their own rules that take precedence over county-level regulations.

The structure (or a group of structures) that conforms to applicable zoning setback requirements but does not satisfy Class A setback requirements. Automatic fire sprinkler system shall be installed in accordance with design standards in section 3805.2. An electrical permit is required for fire sprinklers systems. ... 405.2 Automatic fire sprinklers. The design standards for automatic fire sprinklers for Class B indigenous Hawaiian architecture structures shall be in accordance with NFPA 13. Exception: The design standards for automatic fire sprinklers for Class B indigenous Hawaiian architecture structures shall be permitted as follows: 1. 18 gallons per minute for a single head at 140 square feet maximum coverage of roof area. 2. 13 gallons per minute for each subsequent head at 140 square feet maximum coverage of roof area per head. 3. The minimum supply pressure at the base of the riser shall not be less than 40 pounds per square inch. 4. The minimum residual pressure at the highest sprinkler shall be not less than 12 pounds per square inch. 5. Sprinkler head spacing shall not exceed 14 feet.

Full Breakdown

Section 16.25.405 applies only to hale, the Indigenous Hawaiian architecture structures that Article 4 of Chapter 16.25 allows under the Maui County building code. Table 405.1 sorts every hale into one of two fire protection classes by setback. Class A is a structure, or a group of structures, located at least 100 feet from any existing structure on the same or neighboring properties and at least 100 feet from any property line. Three adjustments apply. Where a property line abuts a public way, the 100 feet is reduced by the width of that way. A property line on the shoreline uses the shoreline setback. A hale ku'ai in the agricultural district that is under 200 square feet, completely open on three sides and used as an agricultural products stand needs only 15 feet from a property line that abuts a public way. Class A structures need no fire protection.

Class B is any hale that conforms to the zoning setbacks but fails the Class A test. A Class B hale must have an automatic fire sprinkler system, and an electrical permit is required for it. Section 405.2 sets the design standard at NFPA 13, then permits a hale-specific alternative. Flow is 18 gallons per minute for the first head covering up to 140 square feet of roof, plus 13 gallons per minute for each further head. Supply pressure at the base of the riser must be at least 40 pounds per square inch, residual pressure at the highest sprinkler at least 12, and head spacing cannot exceed 14 feet. Heads are open type with a 1/2-inch or 17/32-inch orifice and a wax corrosion resistant coating, no more than 6 heads can share a branch, and water density cannot fall below 0.10 gallons per minute per square foot.

The water source can be a domestic meter, detector check meter, underground well, storage tank, swimming pool or pond, but it must deliver 30 minutes of duration. Without a storage tank and booster pump, a 5/8 inch meter supports 1 sprinkler and a 3 inch meter supports 27. Piping is hard drawn copper or coated carbon steel, with plastic allowed only for below grade supply pipes. Smoke detectors at the highest roof points actuate the system, and a local alarm sounds from a smoke detector.

Violations & Fines

The building official can serve a notice of violation or a stop work order on any person responsible, including the property owner, for a hale built without the required sprinkler system. If the notice is ignored, county counsel can be asked to start legal action to restrain, correct or abate the violation. Fines follow the enforcement procedures in sections 19.530.020 and 19.530.030 of the Maui County Code, and each day a violation continues after the correction period counts as a separate offense. Section 405 itself prints no dollar amount.

Frequently Asked Questions

Which Maui County hale need fire sprinklers?
Only Class B hale need sprinklers. A hale is Class B when it conforms to applicable zoning setbacks but is not at least 100 feet from every existing structure and every property line, which is the Class A test. Class A hale that clear that distance need no fire protection under Table 405.1.
Does the 100-foot setback ever shrink?
Yes, in three cases. A property line abutting a public way gets the 100 feet reduced by the width of the public way. A shoreline property line uses the shoreline setback instead. A hale ku'ai under 200 square feet, open on three sides and used as an agricultural products stand in the agricultural district, needs 15 feet from a public-way property line.
How many sprinklers can a domestic water meter support?
Without a storage tank and booster pump, Table 405.2(b) caps the count by meter size: 1 sprinkler on a 5/8 inch meter, 2 on a 3/4 inch meter, 3 on a 1 inch meter, 7 on a 1 1/2 inch meter, 11 on a 2 inch meter and 27 on a 3 inch meter. Table 405.2(a) caps the count by pipe size, from 2 sprinklers on 1 inch pipe to 60 on 3 inch pipe.
What proof of water supply does Maui County require?
Under section 405.3, for any hale that requires fire protection, the applicant must provide a certification from a licensed engineer or a licensed C-20 contractor. It must state that the water supply for the sprinkler system has been tested and can deliver the required fire flow for 30 minutes. Section 405.4 separately requires an approved battery-operated smoke alarm in any hale used for sleeping.

Sources & Official References

Other rules in Maui County

All Maui County rules

Compare Maui County to another location·View the Hawaii building safety overview

Get notified when Fire Sprinkler Requirements in Maui County, HI changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.