Data Centers & Crypto Mining in Stockton, CA (2026)
2 verified data centers & crypto mining rules for Stockton, California, sourced directly from the municipal code and official government pages.
Verified from official government sources
Data Center Zoning & Siting
Stockton has no dedicated data center ordinance and no data center line in Table 2-2. A data center is an industrial use sited in the IL and IG districts. The Director assigns the most similar listed use, setting whether it is by-right or needs a use permit. CEQA applies.
Stockton Data Center Zoning and Siting Rules
Few RestrictionsStockton Municipal Code, Chapter 16.12 (Land Use Permit Requirements), Determination of Allowable Land Uses
If a primary land use is not identified, the Director may determine whether the particular land use is allowable by assigning the land use or activity to a classification that is substantially similar in character. Land uses not listed as being allowed and not substantially similar to an allowed use are prohibited.
Data Center Noise Limits
When a Stockton industrial use abuts homes, its noise cannot exceed 55 dB Leq by day or 45 dB Leq at night at the receiving property line, under Development Code Table 3-7, Part II. A data center's chillers, fans, and generators must meet these limits.
Stockton Data Center Noise Limits
Some RestrictionsStockton Municipal Code, Chapter 16.60 (Noise Standards), Section 16.60.030; limits in Table 3-7, Part II (Section 16.60.040)
If commercial, industrial, or public facilities land uses are adjacent to any noise-sensitive land uses or vacant residential (RE, RL, RM, or RH) or open space (OS) zoning districts, these uses shall comply with the performance standards contained in Table 3-7, Part II.
Looking for San Joaquin County county-wide rules?
County ordinances apply to unincorporated areas and may supplement Stockton city rules.
Data Centers & Crypto Mining in San Joaquin County →