Austin, TX Data Centers & Crypto Mining: Data Center Noise Limits (2026)
Key Facts
- Noise cap
- 70 decibels from mechanical equipment
- Measured at
- Site property line or alleyway shared with a triggering property
- Applies to
- Sites zoned MF-4 or less restrictive within 75 feet of a triggering property
- Triggering property
- 1 to 3 dwelling units, zoned SF-5 or more restrictive
- Screening
- Ground floor and rooftop mechanical equipment hidden from the shared boundary
- Exempt sites
- CBD and DMU zoning, and alterations adding no area or height
- In force
- July 15, 2024 (Ord. No. 20240516-004)
Summary
Austin sets one numeric sound limit that reaches the cooling plant and rooftop units on a data center site: mechanical equipment cannot produce more than 70 decibels, measured at the site's property line or at an alleyway shared with a small residential neighbor. The rule is Land Development Code § 25-2-1063(B), and subsection (E) also requires that ground floor and rooftop mechanical equipment be screened from that boundary.
(A) Exterior lighting must be hooded or shielded so that the light source is not visible from the site's property line or alleyway that is shared with a triggering property. (B) Mechanical equipment may not produce sound in excess of 70 decibels measured at the site's property line or alleyway that is shared with a triggering property. ... (E) Screening Requirements. Except when visible from or through a pedestrian or bicycle access point, the following objects shall be screened and may not be visible at the site's property line or alleyway that is shared with a triggering property: ... (2) ground floor and rooftop mechanical equipment; ... (F) The screening required in Subsection (E) may not impede pedestrian or bicycle access points. (G) Rooftop mechanical equipment may be screened by a parapet. Source: Ord. No. 20240516-004 , Pt. 1, 7-15-24.
Full Breakdown
Section 25-2-1063 sits in Article 10 of Austin's zoning chapter, the compatibility standards that protect small residential lots from larger neighbors. The section never uses the words data center. It regulates mechanical equipment, and the chillers, condensers and rooftop cooling units on a data center site fall inside that category. Subsection (B) is the noise rule: mechanical equipment cannot produce sound in excess of 70 decibels, measured at the site's property line or at an alleyway shared with a triggering property. The section names no weighting scale and no measuring instrument, so the number and the measurement point are the whole standard.
A triggering property is a site with at least one but fewer than four dwelling units that is zoned urban family residence (SF-5) or more restrictive (§ 25-2-1053). Article 10 applies to a site zoned multi-family residence moderate-high density (MF-4) or any less restrictive district when that site is located within 75 feet of a triggering property (§ 25-2-1051). A data center within 75 feet of an SF-5 house or duplex is therefore inside the rule, while the same building farther from every such lot is not.
Section 25-2-1052 carves out structural alterations that do not increase the square footage, area or height of a building, sites zoned central business district (CBD) or downtown mixed-use (DMU), and sites used for duplex, single-family, two-unit, three-unit, adult care or child care purposes.
Beyond the decibel cap, subsection (E) requires ground floor and rooftop mechanical equipment to be screened so it is not visible at the shared property line or alley, except when seen from or through a pedestrian or bicycle access point. Subsection (F) forbids screening that blocks those access points, and subsection (G) allows rooftop equipment to be screened by a parapet. Subsection (A) adds hooded or shielded exterior lighting, subsection (C) keeps a concrete slab for a refuse receptacle at least 15 feet from the triggering property, and subsection (D) keeps resident-only amenities 25 feet away.
The neighboring sections set the geometry. Structures within 50 feet of a triggering property are capped at 40 feet in height and structures from 50 to under 75 feet at 60 feet (§ 25-2-1061), and a compatibility buffer 25 feet wide is required along the shared line, or 15 feet for a site under 75 feet wide (§ 25-2-1062(B)). Council can grant site-specific amendments to height and compatibility buffers under § 25-2-1054, treated as a rezoning, but the 70 decibel limit is not among the items that section lists. Article 10 took effect July 15, 2024 under Ord. No. 20240516-004.
Violations & Fines
Equipment that exceeds 70 decibels at the shared property line or alley, or ground floor and rooftop mechanical equipment that stays visible from that boundary, fails Article 10. The section prints no fine schedule and names no inspector. The standard works as a development requirement, so a project that cannot meet the 70 decibel cap or hide its units from the boundary does not conform to the Land Development Code.
Frequently Asked Questions
Does Austin's code name data centers in its noise rule?
Where is the 70 decibel limit measured?
Does the limit apply to a data center in downtown Austin?
Can rooftop cooling units stay visible from the neighboring lot?
Can City Council waive the compatibility standards?
Sources & Official References
Other rules in Austin
Texas rules heatmap·Compare Austin to another location·View the Texas data centers & crypto mining overview
See something wrong?
Help us keep this page accurate. If you notice an error or outdated information, let us know.