Fulshear, TX Data Centers & Crypto Mining: Data Center Noise Limits (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Daytime limit
85 dB(A)
Nighttime limit
70 dB(A)
Measurement point
60 feet from property line
Penalty
Class C misdemeanor, daily offense
Governing section
City Code § 18-239

Summary

No data-center-specific ordinance exists; Fulshear's citywide noise code caps sound at 85 dB(A) daytime and 70 dB(A) nighttime, measured 60 feet from the property line, and this general limit governs data center cooling and generator noise.

In addition to the violations established by the preceding sections of this article, no person shall conduct, permit, or allow any activity or sound source to produce a sound discernible beyond 60 feet of the property on which the sound is being generated that when measured as provided in section 18-240 exceeds 85 dB(A) during daytime hours and 70 dB(A) during nighttime hours for the respective areas described above.

View official code

Official source re-checked September 7, 2026: no newer edition of the code had been published (publisher’s edition: rev 4849270; v4 updated 2026-05-19).

Full Breakdown

Fulshear's code has no separate data-center use standards, so any data center built here is bound by the citywide noise ordinance. City Code § 18-239 caps sound generated by any activity or source, including cooling towers, chillers, and backup generators, at 85 dB(A) during daytime hours and 70 dB(A) during nighttime hours, measured from the curb line of the nearest public street when the property line is within 60 feet of that street. Readings above those levels are prima facie evidence of a sound nuisance under § 18-239(b), regardless of the type of equipment producing the noise.

Violations & Fines

Exceeding 85 dB(A) daytime or 70 dB(A) nighttime is a Class C misdemeanor under § 18-241, fined per § 1-17; each day of exceedance is a separate offense enforced by city code compliance.

Frequently Asked Questions

Does Fulshear have a noise ordinance specific to data centers?
No. Fulshear regulates all noise sources under one citywide ordinance, City Code § 18-239, which caps sound at 85 dB(A) daytime and 70 dB(A) nighttime: the same limit that applies to any commercial or industrial noise source.
How is data center noise measured for compliance?
A calibrated sound level meter using A-weighting is read from the curb line of the nearest public street, or 60 feet out if the property line is closer, per § 18-240.

Sources & Official References

Other rules in Fulshear

All Fulshear rules

Texas rules heatmap·Compare Fulshear to another location·View the Texas data centers & crypto mining overview

Get notified when Data Center Noise Limits in Fulshear, TX changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.