Aurora, IL Data Centers & Crypto Mining: Data Center Zoning & Siting (2026)

Significant Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified August 2026

Key Facts

Allowed zones
Office, Research, Light Ind., Industrial
Roof-mounted chiller buffer
1,500 feet from residential
Daytime noise limit
57 dB(A), 7am-7pm
Adopting ordinance
Ord. O26-022 (3/24/2026)

Summary

Aurora, Illinois confines data centers to a conditional use in Office, Research, Light Industrial and Industrial zones, with noise, chiller and buffer standards under City Code § 49-104.3.

Data center facility (3305) as shown in Table One: Use Categories and PDD Planned Development Districts within Office, Research, and Light Industrial, and industrial areas under the following conditions... Roof-mounted chillers cannot be located within one thousand five hundred (1,500') feet of any residential, hospital or educational use...

Full Breakdown

Adopted by Ord. O26-022 on March 24, 2026, City Code § 49-104.3 makes Data Center Facilities a conditional use limited to Office, Research, Light Industrial and Industrial districts within PDD Planned Development Districts. Applicants must submit sound, water and energy modeling studies. Roof-mounted chillers must stay 1,500 feet and ground-mounted chillers and generators 1,000 feet from any residential, hospital or educational use; roof-mounted generators and evaporative chillers using potable water are banned outright, and noise is capped at 57 dB(A) daytime and 47 dB(A) nighttime at the property line.

Violations & Fines

Siting or operating a data center outside the approved districts or beyond the noise, buffer or equipment standards is a zoning violation and can block conditional use approval or trigger enforcement action.

Frequently Asked Questions

Where can a data center be built in Aurora, IL?
Only as a conditional use in Office, Research, Light Industrial or Industrial zoning districts within a PDD, per City Code § 49-104.3.
How close can a data center's chillers be to a home in Aurora?
Roof-mounted chillers must be at least 1,500 feet, and ground-mounted chillers at least 1,000 feet, from any residential, hospital or educational use.

Sources & Official References

Other rules in Aurora

All Aurora rules

Compare Aurora to another location·View the Illinois data centers & crypto mining overview

Get notified when Data Center Zoning & Siting in Aurora, IL changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.