Key Facts

Containers under 125 gal
No aboveground setback required
125-500 gal containers
10 ft from buildings/lot lines
501-2,000 gal containers
25 ft from buildings/lot lines
Multi-tank site (501+ gal total)
Rules apply to combined capacity
Vegetation clearance
10 ft around every container

Summary

Mount Vernon's Liquefied Petroleum Gases chapter fixes minimum setback distances for every propane container based on its water capacity, keyed to the nearest building and the adjoining lot line. Bigger tanks need more clearance, and containers must also be spaced apart from each other.

§ 162-5. Location of containers and regulating equipment. A. Each individual container shall be located with respect to the nearest building or group of buildings or lot line of adjoining property which may be built upon in accordance with Table 1: Table 1 Minimum Distances Water Capacity per Container (gallons) Underground Containers (feet) Aboveground Containers (feet) Between Aboveground Containers (feet) Less than 125 10 None None 125 to 250 10 10 None 251 to 500 10 10 3 501 to 2,000 25 25 3 ... If the aggregate water capacity of a multicontainer installation at a consumer site is 501 gallons or greater, the minimum distance shall comply with the appropriate portion of this table, applying the aggregate capacity rather than the capacity per container... F. Readily ignitable material, such as weeds and long dry grass, shall be removed within 10 feet of any container.

Full Breakdown

City Code § 162-5A requires every individual LP-gas container to sit a minimum distance from the nearest building, group of buildings, or lot line of adjoining property that could be built on, set by Table 1 according to water capacity. Containers under 125 gallons need no aboveground clearance at all, but underground containers still need 10 feet. Containers of 125 to 500 gallons need 10 feet from buildings and lot lines aboveground, with 3 feet required between containers over 250 gallons. Containers of 501 to 2,000 gallons need 25 feet from buildings and lot lines, both underground and aboveground, plus 3 feet between containers.

Larger installations scale up further: 50 feet for 2,001 to 30,000 gallons, with 5 feet between containers. If a homeowner or business has several containers on one site totaling 501 gallons or more, § 162-5A requires the distance rules to apply to the combined capacity, not each tank separately, and separate installations must be at least 25 feet apart. Section 162-5F requires clearing readily ignitable material, such as weeds and long dry grass, within 10 feet of any container. Section 162-1 separately requires all LP gas to be effectively odorized so a leak is detectable by smell, and § 162-2 requires container valves, regulators and connectors to carry Underwriters' Laboratories or an equivalent nationally recognized listing before installation.

Violations & Fines

Chapter 162 carries no chapter-specific fine, so the general Code penalty in § 1-4 applies: a fine of up to $250 or up to 15 days in jail for an individual, or up to $500 for a corporation, with each day a violation continues chargeable separately. The City can also bring a court action to compel compliance or enjoin an unsafe installation regardless of any fine paid.

Frequently Asked Questions

How far must a home propane tank be from my house in Mount Vernon?
It depends on size under § 162-5's Table 1. A 125-to-500-gallon tank needs 10 feet from any building or adjoining lot line, and a 501-to-2,000-gallon tank needs 25 feet, measured to the nearest building or buildable lot line.
Do multiple small propane tanks on one property get treated separately?
No. Section 162-5A says once the combined water capacity of the containers at one site reaches 501 gallons, the minimum distances apply to that aggregate total rather than to each tank individually.
Does Mount Vernon require anything besides distance for propane tanks?
Yes. Section 162-1 requires the gas itself to be odorized so a leak is detectable, § 162-2 requires listed valves and regulators, and § 162-5F requires clearing weeds and dry grass within 10 feet of every container.

Sources & Official References

Other rules in Mount Vernon

All Mount Vernon rules

New York rules heatmap·Compare Mount Vernon to another location·View the New York fire regulations overview

Get notified when Propane Storage in Mount Vernon, NY changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Propane Storage in Nearby Cities

How other cities in Westchester County handle propane storage.

Yonkers, NY
Some Restrictions
New Rochelle, NY
Some Restrictions