Skip to main content
CityRuleLookup

Greenburgh, NY Fire Regulations: Smoke Detectors (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Governing section
Greenburgh Code § 100-14
Baseline requirement
smoke/heat detectors, NFPA 72
Multi-family hallway spacing
1 detector per 50 linear feet
Stairwell rule
1 detector at top of each stairwell
Monitoring
central/remote/proprietary station
CO/Certificate of Occupancy tie-in
no C.O. until system approved

Summary

Greenburgh requires every building to have smoke- and heat-detection devices meeting NFPA 72 and the Uniform Code, with multi-family buildings held to added rules: stairwell detectors, hallway spacing every 50 feet and central-station monitoring.

All buildings shall contain smoke- and heat-detection devices in accordance with the Uniform Code, NFPA 72, and § 100-13 of the Code of the Town of Greenburgh. ... All multiple-family residences shall have smoke detectors as follows: (1) One smoke detector at the top of each stairwell open to common hallways or corridors. (2) One smoke detector for each 50 linear feet in common hallways and/or corridors where no point is less than 25 feet from a smoke detector.

View official code

Official source re-checked September 7, 2026: no newer edition of the code had been published (publisher’s edition: rev 4570580; v39 updated 2025-10-22; through 10-22-2025).

Full Breakdown

" Subsection C layers specific rules onto multiple-family residences: one smoke detector at the top of every stairwell open to common hallways or corridors; one smoke detector for every 50 linear feet of common hallway or corridor, positioned so no point is more than 25 feet from a detector; at least one smoke detector in any storage area over 50 square feet, with additional units as the manufacturer's coverage specifications require; smoke detectors connected to a central station, remote station, proprietary station or other NFPA 72 monitoring facility approved by the Fire Marshal; and heat detectors in boiler rooms per NFPA 72 spacing rules.

Subsection D extends the central-station monitoring and full automatic fire alarm requirement, including pull stations, duct detectors and elevator recalls, to buildings used for commercial purposes. Before a Fire Alarm Permit issues, § 100-14B requires the applicant to submit two sets of plans prepared by a New York State licensed engineer, architect or fire protection engineer (or NICET III), along with proof the installer holds a New York State Alarm Installer's License. Section 100-14H bars issuance of a Certificate of Occupancy for any building required to have a fire alarm system until that system is installed, inspected, tested and approved to NFPA and Uniform Code standards.

Violations & Fines

A building found without required smoke- or heat-detection coverage is subject to a Notice of Violation under § 100-26B requiring correction within a stated time, and continued noncompliance carries the same misdemeanor penalties as other Chapter 100 violations: $500 to $1,000 and/or up to three months' imprisonment for a first offense, $750 to $2,500 and/or up to six months for a repeat offense within two years, with each day a separate offense.

Frequently Asked Questions

Does Greenburgh require smoke detectors in every building?
Yes. Section 100-14A requires all buildings to contain smoke- and heat-detection devices in accordance with the Uniform Code and NFPA 72.
What extra smoke detector rules apply to Greenburgh apartment buildings?
Section 100-14C requires a detector at the top of each stairwell open to common hallways, one detector per 50 linear feet of hallway with no point more than 25 feet from a unit, detectors in storage areas over 50 square feet, and central-station monitoring approved by the Fire Marshal.
Can Greenburgh withhold a Certificate of Occupancy over a missing alarm system?
Yes. Section 100-14H bars issuing a Certificate of Occupancy for any building required to have a fire alarm system until the system is installed, inspected, tested and approved under NFPA, Uniform Code and Town Code standards.

Sources & Official References

Other rules in Greenburgh

All Greenburgh rules

New York rules heatmap·Compare Greenburgh to another location·View the New York fire regulations overview

Get notified when Smoke Detectors in Greenburgh, NY changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Smoke Detectors in Nearby Cities

How other cities in Westchester County handle smoke detectors.

Yonkers, NY
Some Restrictions
Mount Vernon, NY
Some Restrictions