Austin, TX Building Safety: Carbon Monoxide Detectors (2026)
Key Facts
- Required occupancies
- Groups I-1, I-2, I-4, R, and E classrooms
- Dwelling placement
- Outside sleeping areas, near bedrooms
- Existing buildings trigger
- Any permitted interior work
- Existing-building alarms
- Battery-operated alarms allowed
- Combination alarms
- UL 217 and UL 2034 listed
- Effective
- July 10, 2025 local amendment
Summary
Austin's local Fire Code amendments require carbon monoxide detection in new residential, institutional and school buildings wherever a fuel-burning appliance, fireplace, forced-air furnace or attached garage is present, and existing Group R, I-1, I-2 and I-4 units must add CO alarms whenever interior work needing a building permit is performed, under Sec. 915 and Sec. 1103.9.
915.1.1 Where required. Carbon monoxide detection shall be provided in Group I-1, I-2, I-4 and R occupancies and in classrooms in Group E occupancies in the locations specified in Section 915.2 where any of the conditions in Sections 915.1.2 through 915.1.6 exist. ... 915.2.1 Dwelling units. Carbon monoxide detection shall be installed in dwelling units outside of each separate sleeping area in the immediate vicinity of the bedrooms. Where a fuel-burning appliance is located within a bedroom or its attached bathroom, carbon monoxide detection shall be installed within the bedroom. ... 1103.9 Carbon monoxide alarms. When interior work requiring a building permit is done in existing Group I-1, I-2, I-4, and R occupancies, they shall be equipped with carbon monoxide alarms in accordance with Section 915 in the unit(s) in which the work was performed, except that the carbon monoxide alarms shall be allowed to be solely battery operated.
Full Breakdown
Section 915 of the local Fire Code amendments (City Code Sec. 25-12-173, effective July 10, 2025) requires carbon monoxide detection "in Group I-1, I-2, I-4 and R occupancies and in classrooms in Group E occupancies" whenever any of several triggers exist: a fuel-burning appliance or fireplace in the unit (Sec. 2), a fuel-burning forced-air furnace serving the unit (Sec. 3), a fuel-burning appliance located elsewhere in the building with a communicating opening (Sec. 4), or an attached private garage (Sec. 5). Where required, Sec. 1 places the detector in dwelling units "outside of each separate sleeping area in the immediate vicinity of the bedrooms," and inside the bedroom itself if a fuel-burning appliance sits in that bedroom or its bathroom.
Group E classrooms need their own detector, and Sec. 3 requires the alarm signal to transmit automatically to a staffed on-site location unless the occupant load is 30 or fewer. 5 requires multiple required alarms in the same unit to be interconnected so one activation sounds all of them, though listed wireless alarms can satisfy that without physical wiring. For existing buildings, Sec. 9 triggers the same detection standard only when interior work requiring a building permit is done in an existing Group I-1, I-2, I-4 or R unit, and it relaxes the hardwiring rule by allowing the replacement alarms to be solely battery operated.
Combination smoke/CO alarms are an acceptable substitute under Sec. 4 if listed to UL 217 and UL 2034, and any alarm or detector that fails or signals end-of-life must be replaced under Sec. 6.
Violations & Fines
Failing to install or maintain required carbon monoxide detection is enforced as a Fire Code violation under City Code Sec. 25-1-462, a misdemeanor prosecuted in Municipal Court, and can also trigger a notice of violation tied to the building permit for the work that triggered the CO requirement under Sec. 1103.9. The fire code official may pursue civil or administrative remedies in addition to a citation under Sec. 113.3.3.2.
Frequently Asked Questions
Does my Austin house need a carbon monoxide detector?
I'm renovating an older Austin home. Do I have to add CO alarms?
Can a combination smoke and carbon monoxide alarm satisfy Austin's requirement?
Sources & Official References
Other rules in Austin
Texas rules heatmap·Compare Austin to another location·View the Texas building safety overview
See something wrong?
Help us keep this page accurate. If you notice an error or outdated information, let us know.