Jefferson Parish, LA Building Safety: Carbon Monoxide Detectors (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Applies to
B&Bs and short-term rentals
Detector type
hardwired, not battery-only
Location
guest room or adjacent hallway
Paired requirement
hardwired smoke detector
Also required
operable fire extinguisher on-site
Checked during
license inspection, Sec. 17.5-4
Noncompliance risk
license refusal or revocation

Summary

Every bed and breakfast and short-term rental in Jefferson Parish must have a hardwired carbon monoxide detector, not just a battery-powered plug-in unit, in each guest room or an adjacent hallway. Section 17.5-2(8) pairs that requirement with a hardwired smoke detector and an operable fire extinguisher on the premises, and it's checked as part of the lodging accommodation license inspection before the property can rent to guests.

These county ordinances apply to unincorporated areas of Jefferson Parish. Incorporated cities within the county may have their own rules that take precedence over county-level regulations.

Sec. 17.5-2. Guest room minimum requirements. No person or lodging accommodation may offer for rent, use, or occupancy any guest room or dwelling unit that does not meet or exceed all applicable building codes, property maintenance laws and state health laws, including but not limited to the following: ...(8)For bed and breakfasts and short-term rentals, a hardwired smoke detector(s) and a hardwired carbon monoxide detector(s) is required in either individual guest room(s) or adjacent hallways. An operable fire extinguisher is required to be located on the premises of the establishment.

View official code

Official source re-checked September 7, 2026: no newer edition of the code had been published (publisher’s edition: Code of Ordinances: Supplement 20 Update 2).

Full Breakdown

Jefferson Parish's carbon monoxide detector rule lives inside the guest room minimum standards for lodging accommodations, not in the general residential building code. 5-2 requires every guest room or dwelling unit offered for rent as a bed and breakfast, hotel, motel, or short-term rental to meet baseline habitability standards, including a proper entry door, a toilet room, a bathtub or shower, and working heating and air conditioning; item (8) of that section adds the life-safety equipment. For bed and breakfasts and short-term rentals specifically, the detector has to be hardwired, wired into the building's electrical system rather than running on a swappable battery, and it must sit in either an individual guest room or an adjacent hallway; the code pairs the carbon monoxide detector requirement with a hardwired smoke detector in the same sentence and adds that an operable fire extinguisher has to be somewhere on the premises.

Hotels and motels get a related but separate requirement in the same section: 24-hour emergency phone access to the front desk and to 911, reflecting that those properties have staff on-site. 5-5. A property that hasn't installed the required detectors can be held up at the licensing stage before it ever gets to open for guests.

Violations & Fines

There's no standalone fine written for a missing detector; instead, failing to meet the guest room standards in section 17.5-2, including the hardwired smoke and carbon monoxide detector requirement, is treated as a failure to comply with chapter 17.5 as a whole. That's grounds under section 17.5-8 for the lodging accommodation review committee or the parish council to suspend or revoke the property's license, and under section 17.5-5 the department of code compliance and enforcement can refuse to issue or renew a license until the property passes inspection.

Frequently Asked Questions

Do short-term rentals in Jefferson Parish need carbon monoxide detectors?
Yes. Section 17.5-2(8) requires a hardwired carbon monoxide detector in either the guest room or an adjacent hallway of any bed and breakfast or short-term rental, paired with a hardwired smoke detector and an operable fire extinguisher on the premises. Inspectors from code compliance and enforcement and the sheriff's office check for this equipment before a lodging accommodation license is issued.
Can I use a battery-powered carbon monoxide detector instead?
No. Section 17.5-2(8) specifically calls for a hardwired detector, not a plug-in or standalone battery unit, in bed and breakfasts and short-term rentals. The requirement sits alongside a hardwired smoke detector in the same sentence of the code, so both devices have to be wired into the property's electrical system.
What happens if my rental doesn't have the required detectors?
The property can fail the inspection required under section 17.5-4 before its lodging accommodation license is issued or renewed, and an existing license can be suspended or revoked under section 17.5-8 for failing to comply with chapter 17.5's requirements, which include the detector rule in section 17.5-2.

Sources & Official References

Other rules in Jefferson Parish

All Jefferson Parish rules

Compare Jefferson Parish to another location·View the Louisiana building safety overview

Get notified when Carbon Monoxide Detectors in Jefferson Parish, LA changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.