Lewis County, WA Data Centers & Crypto Mining: Data Center Noise Limits (2026)
Key Facts
- Governing section
- LCC § 17.142.102(1)
- Enclosure requirement
- All equipment enclosed within a building
- Materials
- Sound-absorptive walls, ceilings and floors
- Barrier height/setback
- 8-foot barrier, set back 10 feet
- Landscaping
- 1 shrub per 10 feet of barrier
Summary
Lewis County requires a data processing center to be fully enclosed with sound-absorptive walls, ceilings and floors, vibration isolation in multi-tenant buildings, and an eight-foot acoustic barrier set back 10 feet from the property line, under LCC § 17.142.102(1).
(1) Noise and Vibration. (a) All equipment associated with the data processing center shall be enclosed within a building(s). (b) Building materials shall include installation of sound-absorptive materials for all walls, ceilings and floors. (c) If the data center is in a multi-tenant building, vibration isolation technology shall be installed in walls or floors that separate the data processing center from other uses. (d) An acoustic barrier or wall at least eight feet tall shall be constructed on all exterior property boundaries, except within 10 feet of a driveway. The barrier or wall shall be set back 10 feet from the abutting property line. Outside the barrier or wall, at least one shrub shall be planted for every 10 horizontal feet of barrier or wall.
Full Breakdown
102(1) is Lewis County's noise and vibration standard for a data processing center sited in unincorporated Lewis County. Every piece of equipment associated with the center has to be enclosed within a building, and the building itself has to use sound-absorptive materials in its walls, ceilings and floors rather than relying only on distance to control noise. Where a data center shares a building with other tenants, the code requires vibration isolation technology in the walls or floors separating the data center use from the rest of the building, so server and cooling equipment vibration doesn't transmit into neighboring tenant space.
Outside the building, the standard adds a physical barrier: an acoustic barrier or wall at least eight feet tall has to run along all exterior property boundaries, except within 10 feet of a driveway, and that barrier itself has to be set back 10 feet from the abutting property line. The code also requires landscaping along the barrier, one shrub for every 10 horizontal feet of wall, so the barrier doesn't read as a blank industrial wall against a rural or small-town streetscape. 102(1) regulates data center noise entirely through enclosure, materials and barrier design rather than a decibel ceiling.
Violations & Fines
A data center sited without the required enclosure, sound-absorptive materials, vibration isolation or acoustic barrier is a Title 17 violation that Community Development can pursue as a civil infraction and misdemeanor under Chapter 1.20 LCC, with each day the site remains out of compliance treated as a separate offense.
Frequently Asked Questions
Is there a decibel limit for data centers in Lewis County?
What barrier does a data center need along its property line?
Does a shared building need extra soundproofing for a data center tenant?