Key Facts

Code
Dev Code Sec. 17.66.050
Residential limit
65 day / 60 night
Simple-tone cut
Minus 5 dBA
Commercial limit
70 day / 65 night
Industrial cap
65 dBA at homes

Summary

Rancho Cucamonga caps residential-property-line noise at 65 dBA daytime and 60 dBA overnight under Development Code Section 17.66.050, and cuts each limit by 5 dBA for continuous simple-tone equipment like data-center chillers and generators.

If the intruding noise source is continuous and cannot reasonably be discontinued or stopped for a time period whereby the ambient noise level can be determined, each of the noise limits above shall be reduced five dBA for noise consisting of impulse or simple tone noise.

Source: Rancho Cucamonga Development Code (Title 17) - Allowed Uses & Performance StandardsView official code

Official source re-checked September 7, 2026: no newer edition of the code had been published (publisher’s edition: rev 4999536; v21 updated 2026-07-15).

Full Breakdown

Development Code Section 17.66.050 sets exterior noise limits at the residential property line: 65 dBA from 7:00 a.m. to 10:00 p.m. and 60 dBA from 10:00 p.m. to 7:00 a.m. When a noise source is continuous and consists of simple-tone or impulse noise-which describes data-center cooling and backup generators-each limit drops 5 dBA, to 60 dBA day and 55 dBA overnight. Commercial and office uses face a 70/65 dBA limit. Industrial performance standards in Table 17.66.110-1 add lot-line caps of 70 to 85 dBA by class, but 65 dBA at any residential property line. The overnight simple-tone floor binds where industrial land meets homes.

Violations & Fines

Noise over the Section 17.66.050 limits is a Development Code violation; the planning director may require the ambient level to be established, and enforcement runs through citations, permit conditions, and abatement.

Frequently Asked Questions

How loud can a data center be in Rancho Cucamonga?
At a home's property line, Development Code Section 17.66.050 caps noise at 65 dBA daytime and 60 dBA overnight. For continuous simple-tone equipment like chillers, each limit drops 5 dBA to 60 and 55.
What noise rule covers data-center chillers and generators in Rancho Cucamonga?
Section 17.66.050 treats steady-tone equipment as simple-tone noise, cutting the residential limit 5 dBA. A continuous chiller or generator near homes must meet 55 dBA overnight at the property line.

Sources & Official References

Other rules in Rancho Cucamonga

All Rancho Cucamonga rules

California rules heatmap·Compare Rancho Cucamonga to another location·View the California data centers & crypto mining overview

Get notified when Data Center Noise Limits in Rancho Cucamonga, CA changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Data Center Noise Limits in Nearby Cities

How other cities in San Bernardino County handle data center noise limits.

Fontana, CA
Some Restrictions
Victorville, CA
Some Restrictions
San Bernardino, CA
Some Restrictions
Ontario, CA
Some Restrictions
Rialto, CA
Significant Restrictions