Santa Monica, CA Data Centers & Crypto Mining: Data Center Noise Limits (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified July 2026

Key Facts

Code
SMMC Chapter 4.12
Residential Zone I
60 dBA day, 50 night
Commercial Zone II
65 dBA day, 60 night
Industrial Zone III
70 dBA anytime
Measured at
Property line, 15-minute Leq

Summary

Santa Monica Municipal Code Chapter 4.12 caps exterior noise at the property line. Residential Zone I limits are 60 dBA daytime and 50 dBA overnight; industrial Zone III is 70 dBA at any hour. A data center's cooling and generators must meet the nearest zone's limit.

no person shall at any location within the City create any noise or allow the creation of any noise on property owned, leased, occupied or otherwise controlled by such person, which causes: The equivalent noise level to exceed the noise standards established in subsection (a) of this Section for the noise zone where the measurement is taken

Source: Santa Monica Municipal Code - Zoning Ordinance (Article 9) & Noise Ordinance (Chapter 4.12)View official code

Full Breakdown

Section 4.12.060 sets exterior noise standards by zone, measured as a 15-minute average (Leq). Residential Zone I allows 60 dBA from 7 a.m. to 10 p.m. and 50 dBA overnight; commercial Zone II allows 65 dBA day and 60 dBA night; manufacturing Zone III allows 70 dBA at any time. Impulsive or tonal noise drops the limit by 5 dBA. Where a parcel lies within 100 feet of a stricter zone, the limit becomes the average of the two. A data center's continuous chillers and backup generators are modeled against the nearest home, so the 50 dBA overnight residential floor governs where IC or OC land abuts housing.

Violations & Fines

Exceeding the Section 4.12.060 limits is a violation enforced by the City's Community Noise Officer through citations, and for a permitted data center, breach of the noise conditions in its Conditional Use Permit.

Frequently Asked Questions

How loud can a data center be in Santa Monica?
On manufacturing Zone III land the exterior limit is 70 dBA at any hour. Where noise reaches homes in Zone I, it drops to 60 dBA daytime and 50 dBA overnight under Section 4.12.060.
What noise rule protects homes near a Santa Monica data center?
Chapter 4.12 sets a 50 dBA overnight cap in residential Zone I and reduces the limit by 5 dBA for tonal noise, so cooling equipment must be engineered to that floor.

Sources & Official References

Other rules in Santa Monica

All Santa Monica rules

California rules heatmap·Compare Santa Monica to another location·View the California data centers & crypto mining overview

Get notified when Data Center Noise Limits in Santa Monica, CA changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Data Center Noise Limits in Nearby Cities

How other cities in Los Angeles County handle data center noise limits.

Lakewood, CA
Light Restrictions
Los Angeles, CA
Some Restrictions
El Monte, CA
Some Restrictions
Pasadena, CA
Some Restrictions
Burbank, CA
Some Restrictions
Downey, CA
Some Restrictions
Santa Clarita, CA
Some Restrictions
Pomona, CA
Some Restrictions