Sangamon County, IL Data Centers & Crypto Mining: Data Center Zoning & Siting (2026)

Significant Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified August 2026

Key Facts

Max height
100 feet
Perimeter setback
150 feet minimum
Residential setback
750 ft (if ≤25 ft tall)
Approval needed
Conditional Permitted Use

Summary

Data centers need a Conditional Permitted Use petition and must meet a 100-foot height cap, a 150-foot perimeter setback, and up to 750 feet of separation from nearby homes.

These county ordinances apply to unincorporated areas of Sangamon County. Incorporated cities within the county may have their own rules that take precedence over county-level regulations.

A. Height. Shall not exceed one hundred (100) feet including any roof-mounted equipment or antennas.

B. Setbacks.

1. Perimeter Setback: The front, side, and rear yard setbacks shall be a minimum of one hundred fifty (150) feet from the property lines which form the outside perimeter of a Data Center Project Area.

2. Residential Structure Setback: Data Centers of twenty-five (25) feet or less in height shall be setback seven hundred fifty (750) feet from the Data Center project property line to a residential structure. Data Centers greater than twenty-five (25) feet in height shall be setback from residential structures thirty (30) times the height of the Data Center. However, suppose the developer of the facility can obtain and record with the Sangamon County Recorder a written, signed, and notarized statement from the owner of the property containing said structure waiving this setback. In that case, the minimum setback from said structure shall be reduced to two hundred (200) feet.

C. Fencing. A fence of at least six (6) feet in height shall enclose and secure the Data Center and must comply with Chapter 17.44.

Full Breakdown

Sangamon County's Data Center chapter, adopted in 2025, caps building height at 100 feet including rooftop equipment and requires a minimum 150-foot setback from the site's own perimeter property lines. Separately, a facility must sit back 750 feet from any residential structure if 25 feet tall or less, or 30 times its height if taller: reducible to 200 feet only if the county records a notarized waiver from the affected homeowner. Beyond these numeric standards, a developer must obtain approval through a Conditional Permitted Use petition to the county, submitting a detailed site plan, utility letters, and County Engineer sign-off on road access before a building permit can issue.

Violations & Fines

Siting or building a data center without an approved Conditional Permitted Use petition, or outside the height/setback standards, is a zoning violation enforceable by the Building and Zoning Department.

Frequently Asked Questions

How far must a data center be from a house in Sangamon County?
750 feet if the facility is 25 feet tall or less, or 30 times the structure's height if taller, unless the homeowner records a signed waiver.
What approval does a data center need before it can be built?
A Conditional Permitted Use petition to the county with a full site plan, utility letters, and County Engineer approval of road access.

Sources & Official References

Other rules in Sangamon County

All Sangamon County rules

Compare Sangamon County to another location·View the Illinois data centers & crypto mining overview

Get notified when Data Center Zoning & Siting in Sangamon County, IL changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Data Center Zoning & Siting in Cities Across Sangamon County