Paola, KS Fence Regulations: Retaining Walls (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified November 2026

Key Facts

Permit exemption
Not over 3 feet, footing bottom to wall top
Exemption lost when
The wall supports a surcharge
Engineered design trigger
More than 48 inches of unbalanced backfill
Lateral support condition
No permanent support at top and bottom
Permit office
Code Official, Community Development Department
Fine on conviction
Not to exceed $500.00

Summary

A retaining wall in Paola that is not over three feet high, measured from the bottom of the footing to the top of the wall, needs no building permit unless it supports a surcharge. Walls outside that exemption fall under the general permit rule, and walls holding more than 48 inches of unbalanced backfill without lateral support need an engineered design.

(b) Work Exempt From Permit. Permits shall not be required for the following. ... (A) Retaining walls that are not over three (3) feet in height measured from the bottom of the footing to the top of the wall, unless supporting a surcharge. ... (B) R404.1.3 Design required. A design in accordance with accepted engineering practice shall be provided for concrete or masonry foundation walls when any of the conditions listed below are found to exist. ... (2) Foundation walls and retaining walls supporting more than forty-eight (48) inches (1,219 mm) of unbalanced backfill that do not have permanent lateral support at the top and bottom.

Full Breakdown

The exemption sits in § 4-105(b)(1)(A) of the Paola City Code. It covers retaining walls not over three feet in height, and the height is measured from the bottom of the footing to the top of the wall, so a deep footing counts toward the three feet. A wall that supports a surcharge loses the exemption at any height. Section 4-105(b) adds that an exemption does not grant authorization for work done in violation of the code. The Land Development Ordinance defines a retaining wall as a wall or similar structural device used at a grade change to hold the soil on the up-hill side from slumping, sliding, or falling.

A wall outside the exemption is a structure covered by the general permit rule in § 4-105(a), which requires the owner or authorized agent to apply to the Code Official first. The application needs construction documents under § 4-106, including a site plan that shows distances from lot lines and the proposed finished grades. The Code Official can require those documents to be prepared by a Kansas registered design professional, and § 4-106(d)(6)(B), written as R404.1.3, requires a design in accordance with accepted engineering practice when retaining walls support more than forty-eight inches of unbalanced backfill and lack permanent lateral support at the top and bottom. The other conditions in that list name foundation walls, such as walls subject to hydrostatic pressure from ground water or exceeding nine feet in height.

After the permit issues, the footing or foundation inspection under § 4-109(c)(1) happens once excavations for footings are complete and any required reinforcing steel and chairs are in place, with forms in place for concrete. Fees follow the valuation of the work under Table 1-A of § 4-301.

Maintenance rules apply to walls that need no permit. Section 8-608(b)(3) lists deteriorated, dilapidated or unsightly fences, walls or retaining walls among the exterior conditions the environmental code treats as unlawful. For a vacant structure, § 4-201(a)(4)(A)(4) requires exterior porches, stairs, landings, retaining walls and other structures to be put in good repair or removed.

Violations & Fines

Building a wall that needs a permit without one exposes the owner to double the normal permit fee under the amended building code section 109.4 and to an investigation fee equal to the permit fee under § 4-301(d). A person convicted of violating Chapter 4 faces a fine not to exceed $500.00, and the City can seek an injunction or mandamus to correct or abate the violation (§ 4-113). A wall left to deteriorate can also be cited as an unlawful exterior condition under § 8-608(b)(3).

Frequently Asked Questions

How tall can a retaining wall be in Paola without a permit?
Not over three feet. Section 4-105(b)(1)(A) measures from the bottom of the footing to the top of the wall, and the exemption does not apply to a wall supporting a surcharge. Even an exempt wall must meet the rest of the code, because the exemption does not authorize work in violation of any provision.
When does a Paola retaining wall need an engineered design?
The code requires a design in accordance with accepted engineering practice for retaining walls supporting more than forty-eight inches of unbalanced backfill that do not have permanent lateral support at the top and bottom. The Code Official can also require construction documents prepared by a Kansas registered design professional where required (§ 4-106(a)).
Does the footing get inspected?
Yes, for walls built under a permit. The footing or foundation inspection is made after excavations for footings are complete and any required reinforcing steel and chairs are in place. The permit holder must notify the Code Official when the work is ready, and work cannot go beyond that point without approval (§ 4-109).
Can the City act on a wall that is falling apart?
Section 8-608(b)(3) names deteriorated, dilapidated or unsightly fences, walls and retaining walls as exterior conditions that count as unlawful under the environmental code. A vacant structure must also have retaining walls put in good repair or removed under § 4-201(a)(4)(A)(4).

Sources & Official References

Other rules in Paola

All Paola rules

Compare Paola to another location·View the Kansas fence regulations overview