Skip to main content
CityRuleLookup

Taylor, TX Fire Regulations: Propane Storage (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Citywide capacity cap
2,000 gal per installation, Fire Code § 6104.2
Indoor storage
Prohibited inside/underneath buildings, § 9-44(b)
Vehicle-fuel tank cap
6,500 gal water capacity, § 9-46(a)(4)
Permit authority
Fire marshal plus city council permit
Inspection fee
$5.00 per piece of equipment
Industrial exception
Cap lifted in industrial-zoned areas

Summary

Taylor's fire code and LP-gas article cap propane storage citywide: liquefied petroleum gas cannot be stored inside or underneath any building, and any single LP-gas installation is limited to 2,000 gallons of water capacity within city limits unless the site is zoned industrial or the fire code official approves otherwise.

(b)The storage of any liquefied petroleum gases in any container, either above ground or underground, is prohibited inside of or underneath any building. No equipment using liquefied petroleum gases except motor vehicles using same as fuel shall be permitted within the fire limits and no equipment used for the purpose of storing wholesale quantities of such gases for wholesale delivery shall be permitted within the city. ... 6104.2 Maximum capacity within established limits. Storage of LP-gas in the aggregate capacity of any one installation shall not exceed a water capacity of 2,000 gallons (7,570 L) within the City limits of the City of Taylor, with the exception of areas that are zoned for industrial use or otherwise approved by the fire code official.

Full Breakdown

Article III of Chapter 9 (Sec. ) has governed liquefied petroleum gas installations in Taylor since 1958. Sec. 9-44(b) flatly bars storing LP-gas in any container, above ground or below, inside or underneath a building, and bars wholesale LP-gas storage equipment anywhere in the city. Piping and appliances must carry Underwriters' Laboratories approval and be 'standard grade' (Sec. 9-44(a), (c)). A gasoline service station wanting to add LP-gas dispensing equipment for vehicle fuel must get a city council permit, keep the storage tank's water capacity at 6,500 gallons or less, and pass inspection by the Railroad Commission of Texas's LP-Gas Division before startup (Sec.

9-46). The city's adopted International Fire Code amendments layer a citywide aggregate cap on top of that: Sec. 2, as amended by Sec. 1(rr), limits the aggregate water capacity of any one LP-gas installation to 2,000 gallons within city limits, with an exception for property zoned industrial or otherwise approved by the fire code official. 00 per piece of equipment applies (Sec. 9-48(a)). Tank trucks and trailers hauling LP-gas may not be parked, stored, or repaired on any street or inside or outside a building within the fire limits (Sec. 9-48(b)).

Violations & Fines

Operating an unpermitted or oversized LP-gas installation, or storing LP-gas inside or beneath a building, violates Chapter 9, Article III. General code penalties in this chapter carry a misdemeanor fine of up to $500 per offense, increased to up to $2,000 per offense for violations touching fire safety, with each day of continued violation a separate offense.

Frequently Asked Questions

How much propane can be stored at one property in Taylor?
Fire Code Sec. 6104.2, as adopted by the city, caps the aggregate water capacity of any single LP-gas installation at 2,000 gallons within city limits, unless the property is zoned industrial or the fire code official approves a larger installation.
Can I store an LP-gas tank inside my garage or basement?
No. Sec. 9-44(b) prohibits storing liquefied petroleum gas in any container, above ground or below, inside or underneath a building anywhere in the city, regardless of tank size.
Does a gas station need special approval to sell propane for vehicle fuel?
Yes. Sec. 9-46 requires a permit from the city council, a tank capacity of 6,500 gallons or less, and inspection approval from the Railroad Commission of Texas's LP-Gas Division before the equipment can operate.
Who inspects LP-gas equipment in Taylor?
The city fire marshal must approve every LP-gas installation before it is used, charging a $5.00 inspection fee per piece of equipment under Sec. 9-48(a).

Sources & Official References

Other rules in Taylor

All Taylor rules

Texas rules heatmap·Compare Taylor to another location·View the Texas fire regulations overview

Get notified when Propane Storage in Taylor, TX changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.