Fort Lauderdale, FL Water Use Rules: Recycled Water Rules (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Governing sections
Code ch. 28, art. III, div. 2, secs. 28-152/153
Residential device
Dual check valve (DuC) required
Non-residential high-hazard device
Reduced pressure principle assembly (RP)
Repair deadline
10 working days after notice
City-ordered repair fee
15% admin fee, 18-month payment plan
Enforcing office
Director of Public Works
Cross-connection rule
Must be eliminated immediately upon discovery

Summary

Fort Lauderdale treats reclaimed water as a cross-connection hazard, not a free substitute for potable supply. Code section 28-153 requires a dual check valve, double check valve or reduced-pressure backflow assembly at every service connection tied to an auxiliary or reclaimed water system, sized to the hazard classification the reclaimed source carries under Chapter 62-610, F.A.C.

Reclaimed water means water that, as a result of treatment of wastewater, is suitable for a direct beneficial use or a controlled use that would not otherwise occur and is not safe for human consumption. [...] Premises where there is an auxiliary or reclaimed water system: At or for a residential service connection: Dual check valve (DuC); At or for a non-residential service connection: Double check valve assembly (DC) if the auxiliary or reclaimed water is a low hazard; or Reduced pressure principle backflow-prevention assembly (RP) if the auxiliary or reclaimed water is a high hazard. [...] Reclaimed water regulated under Part III of Chapter 62-610, F.A.C. is a low hazard unless it is stored with surface water in a pond that is part of a stormwater management system, in which case it is a high hazard.

View official code

Official source re-checked September 7, 2026: no newer edition of the code had been published (publisher’s edition: Code of Ordinances: Supplement 67 Update 1 | Unified Land Development Code: Supplement 58 Update 2).

Full Breakdown

counts as low hazard unless it is co-mingled with surface water in a stormwater pond, which reclassifies it as high hazard. The director of public works (section 28-154) must give written notice to install the required assembly, and under section 28-155 the customer bears the cost of testing, maintenance and any repair, which a licensed plumber or certified backflow tester must complete within ten working days of notice. Installation requires a development services department permit. Cross connections discovered between a reclaimed water system and a customer's plumbing must be eliminated immediately, with no grace period.

The city can also cut off a customer's regular water supply under section 28-190 for 'the lack of backflow prevention assembly, inspection, testing or recertification,' independent of any billing dispute.

Violations & Fines

Failing to install, certify, repair or maintain a backflow assembly, bypassing one, or leaving an unprotected cross connection is a violation under section 28-156, punishable under section 1-6 and/or chapter 11 of the Code. The director gives ten days' written notice to cure; missing it allows discontinuation of water service or city-ordered repairs billed to the owner, spread over 18 months with a 15 percent administrative fee, or a 10 percent fee for a test-only charge, with unpaid balances filed as a property lien.

Frequently Asked Questions

Does Fort Lauderdale require a backflow preventer for reclaimed water?
Yes. Section 28-153(b) requires a dual check valve on a residential service connection tied to an auxiliary or reclaimed water system, and a double check valve or reduced-pressure assembly on a non-residential connection, depending on whether the reclaimed source is classified low or high hazard under Chapter 62-610, F.A.C.
Who classifies a reclaimed water connection as low or high hazard?
The classification follows section 28-152's hazard definitions and section 28-153's footnotes: reclaimed water regulated under Part III of Chapter 62-610, F.A.C. is low hazard unless it is stored with surface water in a stormwater pond, in which case the director of public works treats it as high hazard, requiring a reduced-pressure assembly.
What happens if I do not test or repair my backflow assembly?
The director of public works can shut off your water service for lack of backflow prevention, inspection, testing or recertification under section 28-190, and separately cite you under section 28-156, with repair costs spread over 18 months plus a 15 percent administrative fee if the city ends up doing the work.
Can I install my own backflow prevention assembly?
No. Section 28-155 requires installation by a licensed plumber under a development services department permit, testing by a certified backflow prevention assembly tester, and any repair by a licensed plumber or certified repair technician, completed within ten working days of the city's notice.

Sources & Official References

Other rules in Fort Lauderdale

All Fort Lauderdale rules

Florida rules heatmap·Compare Fort Lauderdale to another location·View the Florida water use rules overview

Get notified when Recycled Water Rules in Fort Lauderdale, FL changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Recycled Water Rules in Nearby Cities

How other cities in Broward County handle recycled water rules.

Pembroke Pines, FL
Light Restrictions
Hollywood, FL
Some Restrictions
Pompano Beach, FL
Some Restrictions
Miramar, FL
Some Restrictions