Maricopa County, AZ Building Safety: Electrical Permits (2026)
Key Facts
- Adopted code
- National Electrical Code, locally amended (Tab J)
- Permit-free exceptions
- 9 narrow categories under §105.2
- Motor exemption threshold
- 50 HP or less, same type/location
- Breaker exemption threshold
- 200 amperes or less, in kind
- Late-start penalty
- Building permit fee doubled (§114.4)
Summary
Unincorporated Maricopa County wires new construction to the National Electrical Code as locally amended by the Local Additions and Addenda. Virtually all electrical work needs a county permit, with nine narrow exceptions carved out, from small motor swaps to Class 2/3 signal wiring.
[A] 105.2 Work exempt from permit... Permits shall not be required for the following:
Electrical:
1. Repair or replacement of motors 50 HP or less, transformers 45 kVA or less, or fixed approved appliances of the same type and rating in the same location.
2. Temporary decorative lighting approved and identified for cord and plug connection.
3. Repair or replacement in kind of any switch, other than a service disconnect, receptacle, contactor, control device or other utilization equipment rated 60 amperes or less.
4. Replacement in kind of any circuit breaker or fuse other than a service disconnect rated 200 amperes or less.
250.118 Types of Equipment Grounding Conductors. The equipment grounding conductor run with or enclosing the circuit conductors shall be one or more or a combination of the following: (4) Electrical metallic tubing with an additional equipment grounding conductor.
Full Breakdown
TA2022001, the county's Local Additions and Addenda effective September 19, 2022, amend the National Electrical Code under Tab J, including §250.118, which lists the types of equipment grounding conductors a circuit can use and adds "electrical metallic tubing with an additional equipment grounding conductor" as an accepted option. Section [A]105.2 spells out what electrical work is exempt from a county permit: repair or replacement of motors of 50 HP or less, transformers of 45 kVA or less, or fixed approved appliances of the same type and rating in the same location; temporary decorative lighting on a cord-and-plug connection; in-kind repair or replacement of switches (other than a service disconnect), receptacles, contactors, control devices or utilization equipment rated 60 amperes or less; in-kind replacement of a circuit breaker or fuse other than a service disconnect rated 200 amperes or less; electrode or transformer replacement for signs or neon tube systems; temporary experimental-lab wiring; temporary wiring for theaters and studios not open to the public; Class 2 and Class 3 control and signal circuits not essential to life safety; and electrical work inside machinery not defined as building service equipment.
Every other electrical installation, alteration or repair, panel upgrades, new circuits, service changes, needs a permit from the Planning and Development Department's Building Official, and that permit lapses after 180 days of inactivity under §[A]105.5. Commencing electrical work before the permit issues carries a penalty equal to the building permit fee doubled under §114.4.
Violations & Fines
Starting electrical work, including panel or service changes, before the permit is issued triggers a fee equal to the building permit fee doubled under §114.4, layered on top of the standard permit fee. The same section subjects anyone doing electrical work contrary to approved plans or a Building Official directive to further penalties prescribed by law.
Frequently Asked Questions
Do I need a permit to replace a circuit breaker in unincorporated Maricopa County?
What electrical code does Maricopa County use?
What's exempt from an electrical permit in unincorporated Maricopa County?