Clark County, NV Building Safety: Fire Sprinkler Requirements (2026)
Key Facts
- IBC buildings
- Sprinklers required at 5,000 square feet of building area or more
- IRC buildings
- Sprinklers required, with no minimum size
- Height trigger
- More than two stories, except Groups R-3 and U
- Group S-1
- Fire area over 12,000 sq ft, or combined over 24,000 sq ft
- Riser room
- At least 16 sq ft, plus 9 sq ft per extra riser
- Enforcing agency
- Clark County Fire Department, Bureau of Fire Prevention
- Adopted
- 2024 IFC as amended by Ord. No. 5321, December 2, 2025
Summary
Clark County requires automatic fire sprinklers throughout every new building built under the International Building Code at 5,000 square feet or more, and in every new building built under the International Residential Code, which covers houses of any size. Any new building more than two stories tall outside Groups R-3 and U is also sprinklered. The Clark County Fire Department's Bureau of Fire Prevention enforces the rule.
903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided throughout all buildings and structures, regardless of occupancy type and including buildings and structures in accordance with the International Residential Code, which meet one of the following requirements, and additionally in the locations described in Sections 903.2.1 through 903.2.12: 1. For buildings constructed in accordance with the International Building Code, approved automatic sprinklers systems are required where the building area is 5,000 square feet ... 2. For buildings constructed in accordance with the International Residential Code, approved automatic sprinkler systems are required. ... 5. In all occupancies except Group R-3, Group U, and occupancies in accordance with the International Residential Code, a building that is more than two stories in height, including any height added by usable floor space, is required to be provided with an automatic sprinkler system throughout.
Official source re-checked September 7, 2026: no newer edition of the code had been published (publisher’s edition: Code of Ordinances: Supplement 147).
Full Breakdown
Section 13.04.110 of the Clark County Code amends Chapter 9 of the 2024 International Fire Code, and its rewrite of IFC 903.2 sets a far lower trigger than the model code. The base rule applies to new buildings and structures of every occupancy type. A building under the International Building Code needs sprinklers at 5,000 square feet of building area. A building under the International Residential Code needs them at any size. The fire code official can also require sprinklers in a building that would otherwise escape them when available fire flow falls short of the code's fire flow requirements, or when the building misses the fire access requirements of Section 503. Outside Group R-3 and Group U, a building more than two stories high, counting height added by usable floor space, is sprinklered throughout.
The exceptions are narrow. Agricultural, livestock and equestrian structures with no perimeter walls, apart from rooms holding required building service components, are exempt if the clear height along the whole perimeter is at least 7 feet 6 inches. Playground shade structures, fuel dispensing canopies and carports are exempt when open to 10 feet of clear height on all sides, built on a noncombustible frame, set 10 feet from the nearest building, property line or shade structure, and under 10,000 square feet of projected area. An addition to an unsprinklered Group R-3 building or IRC dwelling does not force a retrofit when the building has Appendix B fire flow and the new living space is 5,000 square feet or less. Open parking garages of 48,000 square feet or less qualify when nothing is occupied above them and fire apparatus lanes run beside two open sides covering at least 40 percent of the perimeter.
One sprinklered fire area pulls in the rest: if any fire area in a building is sprinklered, required or not, every fire area must be, unless openingless fire walls divide the building into separate buildings under 5,000 square feet each. Occupancy rules add their own triggers. Group E fire areas need sprinklers above 5,000 square feet, on any floor other than the level of exit discharge, or at an occupant load of 300 or more. Daycares open between 12:00 AM and 6:00 AM with 7 or more children are covered. Group S-1 buildings need them when one fire area exceeds 12,000 square feet, sits more than three stories above grade, or when all S-1 areas combined exceed 24,000 square feet. Commercial motor vehicle storage over 5,000 square feet, lithium-ion vehicle storage over 500 square feet and all self-storage also trigger the requirement.
Violations & Fines
The Chief of the Clark County Fire Department and members of the Bureau of Fire Prevention are authorized to serve administrative citations under Title 1, Chapter 1.14 of the Clark County Code and misdemeanor citations under NRS 171.17751 to enforce Title 13 (Section 13.04.050). Section 13.04.110 prints no fine amount. When a required sprinkler system is out of service, the fire department and fire code official must be notified immediately, and the building is evacuated, mitigated or put under an approved fire watch until the system returns to service. Bypassing a fire protection system while the building is occupied is barred unless the fire code official approves an alternative means and methods report.
Frequently Asked Questions
Does a new house in Clark County need fire sprinklers?
If I add to an existing unsprinklered building, does the whole building need sprinklers?
What does a sprinkler riser room have to look like?
Who may design and approve a sprinkler system?
Sources & Official References
Other rules in Clark County
Compare Clark County to another location·View the Nevada building safety overview
See something wrong?
Help us keep this page accurate. If you notice an error or outdated information, let us know.