York County, VA Data Centers & Crypto Mining: Data Center Noise Limits (2026)
Key Facts
- Governing section
- York County Code § 24.1-489.1(f)
- Noise cap
- 55 dBA or 65 dBC, whichever greater
- Measured at
- Property boundary
- Generator testing window
- Mon-Fri, 5-8 p.m.
- Pre-approval requirement
- Ambient noise sound study
Summary
York County caps data center noise at fifty-five A-weighted decibels and sixty-five C-weighted decibels, measured at the property boundary, or the existing ambient level from a required sound study, whichever is greater. Code § 24.1-489.1(f) also limits on-site generator testing to weekday evenings and requires a pre-development sound study.
(f)Data centers shall adhere to the following noise standards(1)A sound study evaluating existing ambient noise prior to project development and modelling predicted noise generation after development, shall be submitted. ... (2)Data centers and associated ancillary equipment shall not produce any sound that exceeds the existing ambient noise captured in the sound study or fifty-five A-weighted decibels (55 dBA) and sixty-five C-weighted decibels (65 dBC), whichever is greater, when measured from the boundary of the property on which it operates. ... (4)Data centers shall only be permitted to engage in on-site generator testing one generator at a time on Monday through Friday from the hours of 5:00 PM to 8:00 PM.
Full Breakdown
York County, Virginia regulates data center noise under Code § 24.1-489.1(f), part of the special use permit standards for these facilities. Before a data center can be approved, the applicant must submit a sound study that measures existing ambient noise, taken between 11:00 p.m. and 5:00 a.m. from at least four corners of the property or other locations the Zoning Administrator sets, and models the noise the completed facility, including its generators and ancillary equipment, is predicted to add. Once operating, the data center and its ancillary equipment cannot produce sound that exceeds the ambient level captured in that study, or fifty-five A-weighted decibels (55 dBA) and sixty-five C-weighted decibels (65 dBC), whichever number is greater, measured from the boundary of the property where the facility sits.
The Zoning Administrator can order additional sound studies after the facility starts operating, at the owner or lessee's expense, to confirm it still meets the noise ordinance and this subsection. All mechanical equipment must stay in good condition and run with a fully operational muffler or other noise-attenuating device where the manufacturer includes one or the sound study required one to hit the decibel limits. Generator testing is tightly limited: only one generator can be tested at a time, and only Monday through Friday between 5:00 p.m. and 8:00 p.m.; outside of testing or commissioning, generators are for backup and emergency use only.
These noise standards apply on top of the required 100-foot non-residential and 500-foot residential structure setbacks and the fifty-foot Type 50 buffer required elsewhere in § 24.1-489.1.
Violations & Fines
A data center that exceeds 55 dBA or 65 dBC at the property boundary, whichever is greater than the ambient level in its sound study, violates § 24.1-489.1(f)(2), and the Zoning Administrator can order a follow-up sound study at the owner's expense to confirm compliance. Testing more than one generator at a time, or running generator tests outside the Monday-through-Friday 5:00 p.m. to 8:00 p.m. window, also violates the ordinance's generator-testing limits.
Frequently Asked Questions
What is the noise limit for a data center in York County?
Does a data center need a noise study before it can open in York County?
When can a York County data center test its backup generators?