Piscataway, NJ Data Centers & Crypto Mining: Data Center Zoning & Siting (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Where data centers are permitted
Warehouse/Light Industrial Redevelopment Overlay Zone only
Max principal building height
60 feet
Setback from street/lot lines
25 feet
Buffer from residential use
200 feet minimum
Overlay floor area cap
2,400,000 sq ft aggregate
Prohibited in overlay
Cellular towers and antennas

Summary

Piscataway Township permits data centers as a principal use only within the Warehouse/Light Industrial Redevelopment Overlay Zone along River Road, defined at Section 21-30.3. The overlay caps commercial building height at 60 feet, requires a 25-foot setback from streets and lot lines, and bars any commercial building within 200 feet of a permitted residential use.

§ 21-30.3. Permitted Principal Uses. ... a. All uses permitted in the LI-1 and LI-5 Zones. b. Data centers. ... § 21-30.6. Maximum Building Height. ... a. No principal commercial building shall exceed 60 feet in height. Mezzanine areas are permitted within the buildings, and shall not be treated as a "story." ... § 21-30.8. Setback Requirements. ... b. No commercial building shall be located within 200 feet of a permitted residential use.

Full Breakdown

Chapter 21, Zoning, defines a DATA CENTER as 'a large group of networked computer servers typically used by organizations for the remote storage, processing, or distribution of large amounts of data' in the Township's general definitions section. That use is a listed permitted principal use only within the Warehouse/Light Industrial Redevelopment Overlay Zone District established by Section 21-30.1 for Block 421.1, Lots 1.03, 1.04 and 6.03 along River Road, an area designated 'in need of redevelopment.' Section 21-30.3 lists data centers alongside self-storage facilities, training centers and limited retail (capped at 2% of gross floor area) as permitted principal uses, on top of everything already allowed in the LI-1 and LI-5 Light Industrial Zones.

A data center sited there is capped by Section 21-30.6 at 60 feet for the principal commercial building, with mezzanine levels not counted as a separate story; accessory buildings are capped at 25 feet and two stories. Section 21-30.7 limits the whole overlay to 2,400,000 square feet of aggregate gross leasable floor area and 25% building coverage. Section 21-30.8 requires a 25-foot setback from all street lines and external lot lines (with an exception allowing a zero-foot line at the Middlesex Borough boundary for cross-boundary development) and bars any commercial building within 200 feet of a permitted residential use.

Cellular towers and antennas are expressly prohibited in the overlay regardless of underlying zoning. Outside this overlay, the Zoning Ordinance's district use tables reviewed for this record do not list data centers as a permitted principal use, so a data center proposed elsewhere in the Township would need a use variance from the Zoning Board of Adjustment.

Violations & Fines

Building a data center outside the Warehouse/Light Industrial Redevelopment Overlay Zone without an approved use variance from the Zoning Board of Adjustment violates the Zoning Ordinance's permitted-use limits. Exceeding the 60-foot principal building height, encroaching within 200 feet of a residential use, or installing a cellular tower or antenna in the overlay violates Sections 21-30.6, 21-30.8 and 21-30.5, enforced by the Zoning Officer through a stop-work order or Municipal Court complaint.

Frequently Asked Questions

Where in Piscataway Township can a data center be built?
Only within the Warehouse/Light Industrial Redevelopment Overlay Zone along River Road, covering Block 421.1, Lots 1.03, 1.04 and 6.03, where Section 21-30.3 lists data centers as a permitted principal use. Elsewhere in the Township, a data center is not a listed use and would need a use variance from the Zoning Board of Adjustment.
How tall can a data center building be?
Section 21-30.6 caps the principal commercial building at 60 feet, though mezzanine levels inside the building are not counted as a separate story. Any accessory building on the same site is capped at 25 feet and two stories.
How close can a data center be to homes?
Section 21-30.8 bars any commercial building in the overlay, including a data center, from being located within 200 feet of a permitted residential use, and requires a 25-foot setback from all street lines and other lot lines.
What does Piscataway's code mean by 'data center'?
Section 21-3's general definitions describe a data center as 'a large group of networked computer servers typically used by organizations for the remote storage, processing, or distribution of large amounts of data,' the term used throughout the Warehouse/Light Industrial Overlay Zone's use list.

Sources & Official References

Other rules in Piscataway

All Piscataway rules

Compare Piscataway to another location·View the New Jersey data centers & crypto mining overview

Get notified when Data Center Zoning & Siting in Piscataway, NJ changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.