Collierville, TN Environmental Rules: Flood Elevation Requirements (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified October 2026

Key Facts

Residential lowest floor
No lower than one foot above base flood elevation
Nonresidential lowest floor
No lower than one foot above base flood elevation
Flood-proofing alternative
Nonresidential in A zones, with engineer or architect certification
Shallow flooding AO and AH, no depth number
At least two feet above highest adjacent grade
Enclosure openings
Two openings, one square inch per square foot enclosed
As-built proof
Elevation certification by surveyor, engineer or architect

Summary

In Collierville's flood hazard areas with base flood elevation data, new or substantially improved residential and nonresidential buildings must have the lowest floor, including basement, elevated no lower than one foot above the base flood elevation. In shallow flooding AO and AH zones, the fallback is at least two feet above the highest adjacent grade.

(a) Residential construction. New construction or substantial improvement to any residential building (or manufactured home) shall have the lowest floor, including basement, elevated no lower than one foot above the base flood elevation. ... (b) Nonresidential construction. New construction or substantial improvement of any commercial, industrial or nonresidential building shall have the lowest floor, including basement, elevated no lower than one foot above the level of the base flood elevation. ... (1) All new construction and substantial improvements of residential buildings shall have the lowest floor, including basement, elevated to the depth number specified on the Flood Insurance Rate Map, in feet, above the highest adjacent grade. If no depth number is specified, the lowest floor, including basement, shall be elevated, at least two feet above the highest adjacent grade.

Full Breakdown

Section 151.100(B)(1) of the Collierville Code of Ordinances governs areas of special flood hazard where base flood elevation data have been provided, including A, A1-30, AE, AO, AH and A99 zones. For residential construction, new construction or substantial improvement to any residential building (or manufactured home) must have the lowest floor, including basement, elevated no lower than one foot above the base flood elevation. Commercial, industrial and other nonresidential buildings follow the same one foot standard.

Nonresidential buildings in A zones have an alternative. They can be flood-proofed in lieu of being elevated, provided all areas of the building below the required elevation are water tight with walls substantially impermeable to the passage of water and built with structural components able to resist hydrostatic and hydrodynamic loads and the effects of buoyancy. A registered professional engineer or architect must certify the standards are met and provide the certification to the Development Director under § 151.099(B)(2).

Manufactured homes follow the same height: the lowest floor must be elevated no lower than one foot above the level of the base flood elevation on a permanent foundation. Elevated buildings with fully enclosed areas below the base flood elevation must be designed to preclude finished living space and allow floodwaters in and out. The openings test is a minimum of two openings with a total net area of not less than one square inch for every square foot of enclosed area, with the bottom of all openings no higher than one foot above grade.

Shallow flooding zones use a different reference. Under § 151.100(D), where base flood depths run one to three feet, the lowest floor must be elevated to the depth number on the Flood Insurance Rate Map, in feet, above the highest adjacent grade, and if no depth number is specified, at least two feet above the highest adjacent grade.

Elevation is checked twice. The application lists the proposed lowest floor elevation relative to mean sea level, and after the lowest floor is placed the permit holder submits an as-built certification under § 151.099(B)(2). The Board of Zoning Appeals handles variances under § 151.101.

Violations & Fines

A building built below the required lowest floor elevation violates § 151.100 and the subchapter's compliance rule in § 151.095. Failure to submit the as-built elevation survey or to make required corrections is cause for a stop-work order under § 151.099(B)(2). Under § 151.102 each day a violation continues is a separate offense, and § 10.99 sets a fine of not more than $50 or the state maximum, whichever is greater.

Frequently Asked Questions

How high above base flood elevation must a Collierville house be built?
Section 151.100(B)(1)(a) requires the lowest floor, including basement, of new or substantially improved residential buildings and manufactured homes to be elevated no lower than one foot above the base flood elevation. If solid foundation perimeter walls are used, openings must allow the unimpeded movement of flood waters.
Can a commercial building flood-proof instead of elevating?
Yes, in A zones. Section 151.100(B)(1)(b) allows nonresidential buildings to be flood-proofed if everything below the required elevation is water tight with walls substantially impermeable to water. A registered professional engineer or architect must certify it, and the certification goes to the Development Director.
Does Collierville ever require two feet above grade?
Yes, in shallow flooding AO and AH zones. If the Flood Insurance Rate Map gives no depth number, § 151.100(D) requires the lowest floor, including basement, to be elevated at least two feet above the highest adjacent grade. Where a depth number is shown, the floor goes that many feet above grade.
What proof of elevation does the Town require?
The permit application lists the proposed lowest floor elevation relative to mean sea level. After the lowest floor is placed, the permit holder submits an as-built certification by a registered land surveyor, professional engineer or architect. Work done before submission is at the permit holder's risk, and missing paperwork can trigger a stop-work order.

Sources & Official References

Other rules in Collierville

All Collierville rules

Compare Collierville to another location·View the Tennessee environmental rules overview

Get notified when Flood Elevation Requirements in Collierville, TN changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Flood Elevation Requirements in Nearby Cities

How other cities in this county handle flood elevation requirements.

Memphis, TN
Some Restrictions