Tracy, CA Environmental Rules: Flood Elevation Requirements (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Required freeboard
1 foot above base flood elevation
Applies to
Lowest floor, including any basement
Certification by
Registered engineer or city building inspector
Enclosed-area flood vents
1 sq in per sq ft, min. 2 openings
Nonresidential alternative
Engineer-certified floodproofing to base flood level

Summary

Section 9.52.150 of the Tracy Municipal Code requires new construction and substantial improvements in the City's special flood hazard areas to have their lowest floor, including any basement, elevated at least one foot above the base flood elevation, certified by a registered engineer or verified by the City's building inspector before the certification goes to the Floodplain Administrator.

9.52.150 - Standards of construction. In all areas of special flood hazard, the following standards shall be required: (c)Elevation and Floodproofing.(1)New construction and substantial improvements shall have the lowest floor elevation, including basement, elevated one foot or higher above the base flood elevation. Nonresidential structures may meet the standards set forth in subsection (3) of this subsection. Upon the completion of the structure, the elevation of the lowest floor, including basement, shall be certified by a registered professional engineer or verified by the community building inspector to be properly elevated. Such certification or verification shall be provided to the Floodplain Administrator.(2)Nonresidential construction shall either be elevated to conform with subsection (1) of this subsection or, together with attendant utility and sanitary facilities:(i)Be floodproofed so that below the base flood level the structure is watertight with walls substantially impermeable to the passage of water;(ii)Have structural components capable of resisting hydrostatic and hydrodynamic loads and effects of buoyancy.

View official code

Official source re-checked September 7, 2026: no newer edition of the code had been published (publisher’s edition: Code of Ordinances: Supplement 69).

Full Breakdown

150 sets Tracy's construction standards for special flood hazard areas across four categories. Under "Anchoring," all new construction and substantial improvements must be adequately anchored against flotation, collapse, or lateral movement from hydrodynamic and hydrostatic loads, including buoyancy. Under "Construction Materials and Methods," flood-resistant materials and methods are required, and electrical, heating, plumbing, and HVAC equipment must be designed or located to keep water out during flooding. The core elevation rule sits in subsection (c): new construction and substantial improvements must have their lowest floor, including any basement, elevated one foot or higher above the base flood elevation, that is, one foot of "freeboard" above the FEMA 100-year flood level, with the finished elevation certified by a registered professional engineer or verified by the community building inspector and filed with the Floodplain Administrator.

Nonresidential structures get an alternative: instead of elevating, they may be floodproofed so the structure is watertight below the base flood level, with walls substantially impermeable to water and structural components able to resist hydrostatic and hydrodynamic loads, again certified by a registered engineer or architect. For enclosed areas below the lowest floor used only for parking, building access, or storage, the design must automatically equalize hydrostatic pressure on exterior walls, meeting either engineer certification or a minimum prescriptive standard: at least two openings totaling one square inch of net area per square foot of enclosed area, split roughly evenly across two separate walls, with the bottom of every opening no higher than one foot above grade. 180.

Violations & Fines

A structure built or substantially improved without the required elevation certificate, engineer's floodproofing certification, or other evidence of compliance with Section 9.52.150 is presumed to be in violation of the chapter until that documentation is provided, per the "Violation" definition in Section 9.52.050. Noncompliance is enforced as an infraction under Section 9.52.070, and the Floodplain Administrator's duties under Section 9.52.140 include taking action to remedy any such violation and obtaining or reasonably utilizing base flood elevation data from federal, state, or other sources when it has not otherwise been provided.

Frequently Asked Questions

How high above the base flood level must a new home's floor sit in Tracy?
At least one foot higher than the base flood elevation, measured to the lowest floor including any basement, under Section 9.52.150(c)(1). A registered professional engineer must certify the finished elevation, or the community building inspector must verify it, and that documentation goes to the Floodplain Administrator.
Can a commercial building in Tracy be floodproofed instead of elevated?
Yes. Section 9.52.150(c)(2) lets nonresidential construction be floodproofed instead of elevated, meaning it is watertight below the base flood level with substantially impermeable walls and structural components able to resist hydrostatic and hydrodynamic loads, certified by a registered engineer or architect.
What are the venting rules for an enclosed garage built below the flood elevation?
Under Section 9.52.150(c)(3), it needs at least two openings totaling one square inch of net area per square foot of enclosed area, spread across two separate walls, with every opening's bottom no more than one foot above grade, unless an engineer certifies an equivalent design.
What proves my Tracy property meets the base flood elevation requirement?
An elevation certification signed by a registered professional engineer, or verification by the community building inspector, filed with the Floodplain Administrator. Without that documentation, Section 9.52.050 presumes the structure is in violation of the chapter.

Sources & Official References

Other rules in Tracy

All Tracy rules

California rules heatmap·Compare Tracy to another location·View the California environmental rules overview

Get notified when Flood Elevation Requirements in Tracy, CA changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.