Wichita, KS Environmental Rules: Flood Elevation Requirements (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Residential freeboard
2 feet above base flood elevation
Non-residential option
2-ft freeboard or certified floodproofing
Enclosure vents
1 sq in per sq ft, 2 openings minimum
Certification required
Licensed land surveyor or professional engineer
Recording
Affidavit filed with Sedgwick County Register of Deeds
Maximum fine
$500 per violation, each day separate

Summary

Wichita requires new or substantially improved homes in the mapped floodplain to raise their lowest floor, including any basement, at least two feet above base flood elevation, and non-residential buildings must either meet that same freeboard or be fully floodproofed. Wichita Municipal Code Sec. 27.06.150 sets the freeboard, floodproofing, and enclosure-venting standards enforced wherever base flood elevation data exists.

New construction or substantial improvements of any residential structures, including manufactured homes, shall have the lowest floor, including basement, elevated a minimum of two (2) feet above base flood elevation. The elevation of the lowest floor shall be certified by a licensed land surveyor or professional engineer. New construction or substantial improvements of any commercial, industrial, or other non-residential structures, including manufactured homes, shall have the lowest floor, including basement, elevated a minimum of two (2) feet above the base flood elevation or, together with attendant utility and sanitary facilities, be floodproofed so that below two (2) feet above the base flood elevation the structure is watertight with walls substantially impermeable to the passage of water and with structural components having the capability of resisting hydrostatic and hydrodynamic loads and effects of buoyancy.

View official code

Official source re-checked September 7, 2026: no newer edition of the code had been published (publisher’s edition: Code of Ordinances: Supplement 35).

Full Breakdown

Sec. 27.06.150 applies in every numbered and unnumbered A, AE, and AH zone where base flood elevation data have been provided under Sec. 27.06.120(b). New construction or substantial improvement of a residential structure, including a manufactured home, must have its lowest floor, including any basement, elevated at least two feet above base flood elevation, with the elevation certified by a licensed land surveyor or professional engineer.

Commercial, industrial, and other non-residential structures, including manufactured homes, face the same two-foot freeboard, or the owner can floodproof the building instead: below the two-foot mark the structure must be watertight, with walls substantially impermeable to water and structural components able to resist hydrostatic and hydrodynamic loads and the effects of buoyancy. A registered professional engineer or architect must certify that the floodproofing meets the standard, and the lowest-floor elevation still must be certified by a licensed surveyor or engineer; both certifications go to the Floodplain Administrator under Sec. 27.06.080(b)(7), (8), and (9).

Fully enclosed areas below the elevated lowest floor that are used only for parking, building access, or storage must let flood water in and out automatically. Absent a licensed engineer's or architect's certified design, the enclosure needs at least two openings with a combined net area of one square inch for every square foot of enclosed area subject to flooding, and the bottom of every opening must sit no higher than one foot above grade; screens, louvers, or valves are allowed if they still let water pass automatically.

Sec. 27.06.110 requires the Administrator to record an affidavit with the Sedgwick County Register of Deeds stating the lowest-floor and floodproofing elevations for every permit issued, at the applicant's expense, so freeboard compliance runs with the land.

Violations & Fines

Sec. 27.06.210 makes noncompliance with the elevation and floodproofing standards a misdemeanor carrying a fine of up to $500.00 per violation, with each day of noncompliance treated as a separate offense. Building below the required freeboard without an approved floodproofing certification also risks the structure's National Flood Insurance Program standing, since the city ties permit issuance to NFIP compliance under Sec. 27.06.010.

Frequently Asked Questions

How high above flood level must I build in Wichita?
Sec. 27.06.150 requires the lowest floor, including any basement, of a new or substantially improved residential structure to sit at least two feet above base flood elevation, certified by a licensed land surveyor or professional engineer before the city signs off.
Can a commercial building skip the elevation requirement?
Only if it is floodproofed instead: below two feet above base flood elevation the structure must be watertight, with impermeable walls and components rated to resist hydrostatic and hydrodynamic loads, certified by a registered professional engineer or architect under Sec. 27.06.150(b).
Do enclosed areas under an elevated house need vents?
Yes. Sec. 27.06.150(c) requires enclosed areas below the lowest floor used for parking, access, or storage to have at least two openings totaling one square inch per square foot of enclosed area, with each opening's bottom no more than one foot above grade.
Is my elevation certificate kept on public record?
Yes. Sec. 27.06.110 requires the Floodplain Administrator to record an affidavit with the Sedgwick County Register of Deeds listing the lowest-floor and floodproofing elevations, the legal description, and the owner's name for every permit issued, at the applicant's expense.

Sources & Official References

Other rules in Wichita

All Wichita rules

Compare Wichita to another location·View the Kansas environmental rules overview

Get notified when Flood Elevation Requirements in Wichita, KS changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.