Propane/LP-gas storage in unincorporated Riverside County follows the adopted California Fire Code Chapter 61 (Ord. 787). Above-ground tanks of 501β2,000 gallons must sit at least 10 feet from buildings and lot lines; underground tanks at least 10 feet. Larger installations require permits and construction documents. In wildfire defensible-space zones, tanks need 10 feet of clearance to bare soil.
Storage and use of liquefied petroleum gas (propane) in unincorporated Riverside County is regulated by Chapter 61 of the California Fire Code, adopted via Ordinance 787, plus NFPA 58. Under CFC Table 6104.3, minimum separation distances for above-ground ASME containers depend on capacity: containers from 501 to 2,000 gallons water capacity must be at least 10 feet from buildings and from the lot line of adjoining property that can be built upon (and 25 feet between containers); containers from 251 to 500 gallons must be at least 10 feet from buildings/lot lines; and smaller containers under 125 gallons must generally be 10 feet from buildings. All parts of an underground LP-gas container must be at least 10 feet from a building or buildable lot line. Per CFC Section 6101.3, when a single container exceeds 2,000 gallons water capacity, or the aggregate exceeds 4,000 gallons, the installer must submit construction documents. Permits are required per CFC 6101.2 (referencing Sections 105.5/105.6). Portable cylinders in buildings are restricted (Section 6103.2.1), and cylinder storage is governed by Section 6109. Separately, for wildfire safety, California defensible-space guidance (PRC 4291, Zone 2) directs maintaining roughly 10 feet of clearance to bare mineral soil around propane tanks. Always confirm tank siting and permit needs with Riverside County Fire before installation.
LP-gas Fire Code violations are enforced under Ordinance 787, Section 112.4 (penalties per Riverside County Ord. 725 and HSC 17995β17995.5). Installing or operating a regulated LP-gas system without a required permit, or with inadequate setbacks, can require correction/abatement and re-inspection. Tanks in fire hazard severity zones must also meet defensible-space clearance.
Other ordinances people look up for this city. Green dot = verified primary-source excerpt.
Corona, CA
Corona Municipal Code Title 6 prohibits dogs from barking, howling, or making noise that disturbs neighbors for sustained or repeated periods. Riverside Coun...
Corona, CA
Corona regulates leaf blowers under its general noise ordinance in Corona Municipal Code Chapter 9.36, restricting use during early morning, evening, and nig...
Corona, CA
Corona allows wood, vinyl, masonry block, wrought iron, tubular steel, and stucco fences in residential zones. Barbed wire, razor wire, electric fences, and ...
Corona, CA
Corona requires dogs to be on a leash no more than 6 feet long when off the owner's property, in public spaces, and in city parks. Off-leash areas are limite...
Corona, CA
Corona generally restricts chickens and livestock to agricultural and equestrian zones, with limited allowances in some single-family residential zones depen...
Corona, CA
California Civil Code 4735 and 714.1 protect artificial turf in Corona; HOAs cannot ban it. Most residential installs need no permit but must meet drainage a...
Side-by-side rule comparisons with other cities in Riverside County.
See how other cities in Riverside County handle propane storage.
See how Corona's propane storage rules stack up against other locations.
Quick Compare
Help us keep this page accurate. If you notice an error or outdated information, let us know.