Everett, WA Outdoor Lighting: Dark Sky Rules (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified August 2026

Key Facts

Applies to
LI/HI zones, Central Waterfront Planning Area only
Minimum lighting
0.5 foot-candle, public areas
Maximum lighting
4 foot-candles, high-traffic areas
Fixture mounting cap
30 feet, full cut-off, dark-sky rated
Wall-mounted lot lighting
Prohibited outright
Default penalty
$250/violation/day (Ch. 1.20 EMC)

Summary

Inside Everett's Central Waterfront Planning Area, in the Light Industrial and Heavy Industrial zones, site lighting must meet dark-sky standards under Everett Municipal Code 19.09.310(C): capped foot-candle levels, full cut-off fixtures, and a ban on light trespass past the property line.

C. Lighting and Glare in Central Waterfront Planning Area. Development within the Central Waterfront Planning Area (see Map 9-3) is required to meet the site lighting standards in this subsection... 2. Standards. a. All site lighting shall meet dark-sky standards. b. Site Lighting Levels. All publicly accessible areas shall be lighted with average minimum and maximum levels as follows: (1) Minimum of one-half foot-candle; (2) Maximum (for high volume pedestrian areas and building entries) of four foot-candles... d. Parking area lighting fixtures shall be full cut-off (zero percent candlepower at ninety degrees horizontal and ten percent maximum candlepower at eighty degrees from vertical), dark-sky rated, and mounted no more than thirty feet above the ground... g. Lighting must not trespass onto adjacent private parcels, nor shall a light source (luminaire) be visible at the property line. All building lights shall be directed onto the building itself and/or the ground immediately adjacent to it. The light emissions shall not be visible above the roofline of the building. h. Building wall mounted parking lot lighting is prohibited.

View official code

Official source re-checked September 8, 2026: no newer edition of the code had been published (publisher’s edition: current through Ordinance 4194-26, passed July 29, 2026).

Full Breakdown

310(C) sets binding lighting standards for development inside the Central Waterfront Planning Area shown on the code's Map 9-3, an overlay covering the LI and HI zones along the waterfront. All publicly accessible areas must be lit to an average minimum of one-half foot-candle and a maximum of four foot-candles in high-volume pedestrian areas and building entries. Parking-area fixtures must be full cut-off (zero percent candlepower at 90 degrees horizontal, no more than 10 percent candlepower at 80 degrees from vertical), dark-sky rated, and mounted no higher than 30 feet, with lower mounting preferred to keep a human scale.

Parking lighting within 300 feet of residentially zoned land must sit on standards no taller than 20 feet, or the height of any intervening building, whichever is taller. Pedestrian-scale fixtures of 15 feet or less are encouraged near foot traffic. Light sources cannot be visible at the property line, building lights must aim onto the building or the ground next to it, emissions cannot show above the roofline, and wall-mounted parking-lot lighting on buildings is flatly prohibited. Any permit application that includes site lighting must submit a lighting plan showing compliance before approval, reviewed by the planning department.

09, Urban Development Standards, and only bind projects within the mapped Central Waterfront area; industrial or commercial lighting elsewhere in the LI/HI zones is not held to this dark-sky test.

Violations & Fines

Noncompliant lighting plans are held at permit review and won't clear submittal until they meet the foot-candle and fixture specs. Built-out violations run through Chapter 1.20 EMC, Everett's citywide code enforcement chapter covering Title 19: a code enforcement officer can issue a notice and order, and unresolved violations accrue a $250-per-violation, per-day civil penalty (rising to $500 per day for repeat violators) until the fixtures are brought into compliance.

Frequently Asked Questions

Does Everett's dark-sky rule apply citywide?
No. It applies only inside the Central Waterfront Planning Area shown on the code's Map 9-3, within the Light Industrial and Heavy Industrial zones. Development outside that mapped area is not held to the dark-sky foot-candle and fixture standards in EMC 19.09.310(C).
What fixtures satisfy the standard?
Parking-area fixtures must be full cut-off, meaning zero percent candlepower at 90 degrees horizontal and no more than 10 percent at 80 degrees from vertical, dark-sky rated, and mounted no higher than 30 feet above grade, per EMC 19.09.310(C)(2)(d).
Can a building mount lights on its exterior wall to light a parking lot?
No. EMC 19.09.310(C)(2)(h) prohibits building wall-mounted parking lot lighting outright within the Central Waterfront Planning Area, regardless of whether the fixture is otherwise shielded.
Who reviews compliance before a permit issues?
A lighting plan demonstrating compliance with EMC 19.09.310(C) must be submitted for review and approval at the time of any permit application that includes site lighting, per EMC 19.09.310(C)(3).

Sources & Official References

Other rules in Everett

All Everett rules

Compare Everett to another location·View the Washington outdoor lighting overview

Get notified when Dark Sky Rules in Everett, WA changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Dark Sky Rules in Nearby Cities

How other cities in Snohomish County handle dark sky rules.

Lynnwood, WA
Some Restrictions
Marysville, WA
Some Restrictions