East Brunswick, NJ Outdoor Lighting: Light Trespass & Shielding (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified October 2026

Key Facts

Light spillage limit
No greater than 0.1 footcandles from a property
Direction
All lighting must be directed into the site
Minimum and average levels
0.50 footcandles minimum, 0.75 average, vehicular and pedestrian areas
Mounting height
Building height or twenty-five (25) feet, whichever is less
Visible-source fixtures
Building mounted fixtures with visible source are prohibited
Applies through
Site plan, P.U.R.D. and subdivision review under Chapter 192

Summary

In East Brunswick Township, lighting designed for site plan, planned unit residential and subdivision development must be directed into the site, and spillage of light from a property cannot exceed 0.1 footcandles under § 192-39(D). Section 192-12 adds that directional lights be arranged to minimize glare and reflections on adjacent properties.

C. Height. Mounting height shall not exceed the height of the building or twenty-five (25) feet, whichever is less. D. Standards. Distribution of lighting shall be even throughout the site. All lighting shall be designed to provide a minimum of 0.50 footcandles and an average of 0.75 footcandles throughout all vehicular and pedestrian areas. Spillage of light from a property may be no greater than 0.1 footcandles. All lighting must be directed into the site. All lighting shall be provided by stanchion mounted fixtures or bollards and serviced underground. Building mounted fixtures, where the light source is visible, are prohibited. ... G. Isofootcandles Plotted. A point by point lighting analysis with a maximum grid of ten (10') foot by ten (10') foot shall be provided on a lighting plan indicating footcandle levels of existing and proposed lighting.

Full Breakdown

Chapter 192, Design Guidelines & Standards, states in § 192-1 that it provides guidelines for site plan, P.U.R.D. and subdivision design. The lighting standard in § 192-39, amended 11-24-2014 by Ord. No. 14-13, sits inside that chapter, so it is applied by the Planning Board or Zoning Board when a development is reviewed.

Subsection D sets the numbers. Distribution of lighting is even throughout the site, with a minimum of 0.50 footcandles and an average of 0.75 footcandles throughout all vehicular and pedestrian areas. Spillage of light from a property is limited to no more than 0.1 footcandles, and all lighting must be directed into the site. Fixtures are stanchion mounted or bollards serviced underground, and building mounted fixtures where the light source is visible are prohibited. Subsection C caps mounting height at the height of the building or twenty-five (25) feet, whichever is less. Subsection G requires a point by point lighting analysis with a maximum grid of ten (10') foot by ten (10') foot on a lighting plan showing footcandle levels of existing and proposed lighting; subsections E and F add the manufacturer and number of each fixture and a detail of the fixture and pole.

Other sections in the chapter push the same direction. Section 192-12 requires directional lights arranged to minimize glare and reflections on adjacent properties. Section 192-13 calls for perimeter buffering to minimize off-site glare from vehicle headlights and light from structures. Section 192-7 directs that streets, lots, parking areas and buildings mitigate adverse effects of glare on neighboring properties. Under § 192-4, the Planning or Zoning Board can waive a requirement where literal enforcement is impracticable or will exact undue hardship, and § 192-2 lets the approving Board apply more stringent requirements.

Violations & Fines

Section 192-39 prints no fine of its own. The standard is enforced through the approved plan: the manufacturer, fixture detail and lighting analysis go on the plans, and § 166-13 requires lighting in all commercial parking areas to be maintained and replaced immediately on an on-going basis, in conformance with site plan approval, with owners and tenants of commercial uses responsible for the poles, stanchions, bulbs, starters and ballasts.

Frequently Asked Questions

What is the light spillage limit in East Brunswick Township?
Section 192-39(D) says spillage of light from a property may be no greater than 0.1 footcandles, and that all lighting must be directed into the site. The same subsection requires a minimum of 0.50 footcandles and an average of 0.75 footcandles throughout vehicular and pedestrian areas.
How high can a site light pole be?
Under § 192-39(C), mounting height cannot exceed the height of the building or twenty-five (25) feet, whichever is less. Fixtures are stanchion mounted or bollards serviced underground, and building mounted fixtures where the light source is visible are prohibited.
What proof of compliance does the Township require?
Section 192-39(G) requires a point by point lighting analysis with a maximum grid of ten (10') foot by ten (10') foot on a lighting plan, showing footcandle levels of existing and proposed lighting. Subsections E and F also require the manufacturer and number of each fixture and a detail of the fixture and pole.
Does the Code address glare toward neighbors apart from the footcandle limit?
Yes. Section 192-12 says directional lights shall be arranged to minimize glare and reflections on adjacent properties, and § 192-13 requires buffering around the site perimeter to minimize off-site glare from vehicle headlights and light from structures.

Sources & Official References

Other rules in East Brunswick

All East Brunswick rules

Compare East Brunswick to another location·View the New Jersey outdoor lighting overview

Get notified when Light Trespass & Shielding in East Brunswick, NJ changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Light Trespass & Shielding in Nearby Cities

How other cities in this county handle light trespass & shielding.

Edison, NJ
Some Restrictions