Santa Fe, NM Building Safety: Carbon Monoxide Detectors (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Governing section
§ 11.901.12, Residential Addition and Remodel Green Building Code
Adopted by
Subsection 7-4.3 SFCC 1987
Triggers when
Remodel/addition affects 50%+ of floor area
Required certification
CSA 6.19 or UL 2034
Minimum sensitivity
One alarm detects CO as low as 9 ppm
Exception
No garage, no gas or solid-fuel appliances

Summary

Santa Fe's Residential Addition and Remodel Green Building Code makes carbon monoxide alarms mandatory in additions and remodels that touch 50% or more of a single-family home's floor area. Section 11.901.12 requires a CO alarm outside every sleeping area, hard-wired with battery backup where wiring exists, and certified to CSA 6.19 or UL 2034.

11.901.12 Carbon monoxide (CO) alarms. A carbon monoxide (CO) alarm is installed in a central location outside of each separate sleeping area in the immediate vicinity of the bedrooms. The CO alarm(s) is located in accordance with NFPA 720 and where there is existing electrical lines accessible is hard-wired with a battery back-up. The alarm device(s) is certified by a third-party for conformance to either CSA 6.19 or UL 2034. At least one of the CO alarms is capable of detecting CO concentrations as low as 9 ppm and includes a visible display. Mandatory Exception: No CO alarms are required when all three of the following conditions are true: 1. The is no attached garage; 2. There are no gas-fired appliances within the conditioned space and; 3. There are no solid fuel burning appliances in the home, including fireplaces.

Full Breakdown

3 SFCC 1987 adopts the Santa Fe Residential Addition and Remodel Green Building Code, which applies to additions and remodels affecting 50 percent or more of the floor area of an attached or detached single-family residence. 12, 'Carbon monoxide (CO) alarms,' is marked Mandatory: a CO alarm must be installed in a central location outside each separate sleeping area, in the immediate vicinity of the bedrooms, located in accordance with NFPA 720. Where existing electrical lines are accessible, the alarm must be hard-wired with a battery backup.

19 or UL 2034, and at least one alarm in the home must be able to detect CO concentrations as low as 9 ppm and include a visible display. The section carves out a narrow exception: no CO alarm is required at all if three conditions are all true at once: the home has no attached garage, has no gas-fired appliances inside the conditioned space, and has no solid fuel-burning appliances, including fireplaces. 4.

Violations & Fines

A remodel or addition that meets the 50-percent-of-floor-area trigger cannot pass its Green Building Code compliance review, and therefore cannot get final planning and land use department signoff, without the mandatory CO alarm in place, unless the narrow no-garage, no-gas-appliance, no-solid-fuel exception applies. Missing or uncertified alarms are treated as an unmet mandatory practice under Section 11.305.3.3, holding up the project's final inspection.

Frequently Asked Questions

Does Santa Fe require CO alarms in home remodels?
Yes, if the project touches 50 percent or more of the home's floor area. Section 11.901.12 of the Residential Addition and Remodel Green Building Code makes a certified CO alarm mandatory outside each sleeping area, unless the home has no attached garage and no gas or solid-fuel-burning appliances at all.
Where must the carbon monoxide alarm be placed?
In a central location outside each separate sleeping area, in the immediate vicinity of the bedrooms, positioned in accordance with NFPA 720. Where existing wiring is accessible, the alarm must be hard-wired with a battery backup rather than running on batteries alone.
What certification must the alarm carry?
Every CO alarm installed under Section 11.901.12 must be third-party certified to either CSA 6.19 or UL 2034, and at least one alarm in the home must detect concentrations as low as 9 ppm and show a visible digital readout.

Sources & Official References

Other rules in Santa Fe

All Santa Fe rules

Compare Santa Fe to another location·View the New Mexico building safety overview

Get notified when Carbon Monoxide Detectors in Santa Fe, NM changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.