Bothell, WA Building Safety: Fire Sprinkler Requirements (2026)

Significant Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified October 2026

Key Facts

Base rule
Sprinklers throughout every building with a Group R fire area (Section 903.2.8)
One- and two-family (R-3)
System under Section 903.3.1.3 is permitted
Townhouse trigger
Three or more townhouses with common walls, or over 5,000 sq ft or 40 ft high
R-2 multifamily trigger
Over 5,000 sq ft of floor area or over 40 ft in height
Care facility trigger
Five or more individuals in a single-family IRC dwelling
Penalty
Misdemeanor per BMC 20.08.100, punished under BMC 1.24.010

Summary

In the City of Bothell, Washington, Bothell Municipal Code § 20.08.061 rewrites International Fire Code Section 903.2.8 so that an automatic sprinkler system goes throughout every building with a Group R fire area. Group R-3 homes can use a system under Section 903.3.1.3, while townhouse and multifamily buildings face size and height triggers.

903.2.8 Group R Occupancies An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R fire area. EXCEPTIONS: Group R-1 if all of the following conditions apply: 1. The Group R fire area is no more than 500 ft2 (46 m2) and is used for recreational use only. ... 903.2.8.1 Group R-3 An automatic sprinkler system installed in accordance with Section 903.3.1.3 shall be permitted in Group R-3 occupancies. ... 903.2.8. ... 5 Adult Family Homes An adult family home that serves residents who require assistance during an evacuation must install an automatic sprinkler system that meets the requirements of NFPA 13D. EXCEPTION: Existing adult family homes shall not be required to retrofit a residential sprinkler system. 903.2.8.6 Townhouses When a building has three or more townhouses constructed with common walls or the aggregate structure size (which includes all of the townhouses in one structure) exceeds 5,000 ft2 (465 m2) of floor area or more than 40 ft (12.9 meters) in height;

Full Breakdown

The Bothell City Council amends the International Fire Code, as adopted by BMC 20.08.040, one chapter at a time, and BMC 20.08.061 covers Chapter 9. The amended Section 903.2.8 sets the baseline: an automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R fire area. The only exception printed in that section is for a Group R-1 fire area of no more than 500 square feet used for recreational use only, on one story, with no basement, no closer than 30 feet to another structure, no cooking, an occupant load of no more than 8, and a hand-held extinguisher in every Group R fire area.

Section 903.2.8.1 then permits a system installed under Section 903.3.1.3 in Group R-3 occupancies, which BMC 20.08 defines as one- and two-family dwellings as identified by the IRC. The same chapter labels Section 903.3.1.3 as NFPA 13D and drops the water-supply buffer for systems designed under it. Section 903.2.8.6 reaches a building with three or more townhouses built with common walls, or an aggregate structure over 5,000 square feet of floor area or more than 40 feet in height. Section 903.2.8.7 applies the same 5,000 square foot and 40 foot triggers to an R-2 multifamily building.

Care uses carry their own rules. Section 903.2.8.4 requires a Section 903.3.1.3 system in licensed care facilities with five or more individuals in a single-family IRC dwelling, and converting a single-family dwelling into one needs a retrofit. An adult family home serving residents who need help during an evacuation must install an NFPA 13D system, but existing adult family homes do not have to retrofit.

Section 903.2 adds that where Chapter 9 and Chapter 20.08 BMC conflict, the most restrictive requirement applies. Under BMC 20.08.090, one- and two-family dwellings used solely as a private residence skip Fire Prevention plan review, yet a plan review fee for the sprinkler system is still charged under the city fee schedule when one is required.

Violations & Fines

Under BMC 20.08.100, violating Chapter 20.08 BMC or an order made under it is a misdemeanor for each violation, punished as set forth in BMC 1.24.010, and each day a violation continues is a separate offense unless otherwise specified. The penalty does not excuse the violation: the person must correct it immediately, and the city can still enforce removal of prohibited conditions. Under Section 901.7.6.1, failing to meet fire watch requirements while a required sprinkler system is out of service can bring a fire watch code case and fines.

Frequently Asked Questions

Does a new single-family house in the City of Bothell need sprinklers?
Section 903.2.8 requires a system throughout all buildings with a Group R fire area, and Section 903.2.8.1 permits a Section 903.3.1.3 system in Group R-3 occupancies, defined as one- and two-family dwellings as identified by the IRC. The only exception printed in BMC 20.08.061 for Group R is the small recreational R-1 fire area, not a house.
When does a townhouse building in Bothell need sprinklers?
Section 903.2.8.6 applies when a building has three or more townhouses constructed with common walls, or when the aggregate structure, counting all townhouses in one structure, exceeds 5,000 square feet of floor area or is more than 40 feet in height. Section 903.2.8 also requires sprinklers throughout buildings with a Group R fire area.
Can the Bothell Fire Marshal waive sprinklers in part of a building?
Section 903.2 lets sprinklers be omitted in certain rooms or areas, subject to the approval of the Fire Marshal with the concurrence of the Building Official. Listed cases include rooms where water creates a serious fire or life hazard, such as aluminum powder or calcium carbide storage, and vaults of fire resistive construction used for records.
Do house sprinkler plans get a fire plan review in Bothell?
BMC 20.08.090 exempts Group R-3 occupancies and one- and two-family dwellings used solely as a private residence from fire prevention division plan review. If a fire sprinkler system is required, a plan review fee for that system is still charged as identified in the city's fee schedule.

Sources & Official References

Other rules in Bothell

All Bothell rules

Compare Bothell to another location·View the Washington building safety overview

Get notified when Fire Sprinkler Requirements in Bothell, WA changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Fire Sprinkler Requirements in Nearby Cities

How other cities in King County handle fire sprinkler requirements.

Auburn, WA
Heavy Restrictions
Bellevue, WA
Some Restrictions
Federal Way, WA
Some Restrictions
Kirkland, WA
Light Restrictions
Renton, WA
Some Restrictions