Chino, CA Building Safety: Fire Sprinkler Requirements (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Trigger
5,000+ sq ft new building
Addition trigger
5,000+ sq ft addition
Group R-3 homes
expressly excluded
Alternates
allowed with fire marshal approval

Summary

Chino requires automatic fire sprinklers in new buildings of 5,000 square feet or more, but its local amendment expressly excludes one- and two-family homes and their accessory structures.

In addition to the requirements of Section 903, fire sprinklers are required for the construction of buildings five thousand square feet or more, regardless of fire walls, except for Group R-3 (one- and two-family dwelling) and Group U accessory to Group R-3 occupancies.

Fire sprinklers are required when additions exceed five thousand square feet. When the addition is less than fifty percent of the original building square footage, the addition shall be equipped with a sprinkler system. When the addition is fifty percent or greater than the original building square footage, the entire structure shall be equipped with a sprinkler system.

Alternate automatic fire extinguishing systems complying with sections 904 of the California Building Code may be permitted in lieu of automatic sprinkler protection where recognized and approved by the building official and the fire marshall.

(Ord. 2022-015, § 1, 7-19-2022.)

View official code

Official source re-checked September 7, 2026: no newer edition of the code had been published (publisher’s edition: Code of Ordinances: Supplement 38).

Full Breakdown

Chino's amendment to California Building Code § 903.2 requires fire sprinklers for the construction of any building of 5,000 square feet or more, regardless of fire walls, but Group R-3 (one- and two-family dwellings) and Group U structures accessory to R-3 are expressly excluded from this local trigger. Additions of 5,000 square feet or more also trigger sprinklers, and if the addition is 50% or more of the original building's square footage, the entire structure must be sprinklered. Alternate extinguishing systems may be approved by the building official and fire marshal in lieu of sprinklers.

Violations & Fines

Constructing or adding to a qualifying building without the required sprinkler system violates Chino's amended Building Code and can result in a stop-work order, correction notice, or denial of final inspection and occupancy.

Frequently Asked Questions

Do single-family homes in Chino need fire sprinklers under this local rule?
No. Chino's amendment to CBC § 903.2 expressly excludes Group R-3 one- and two-family dwellings and their Group U accessory structures from this size-based trigger.
What size building triggers Chino's sprinkler requirement?
Any new building of 5,000 square feet or more, or an addition of 5,000 square feet or more, per Chino Municipal Code § 15.04.050.

Sources & Official References

Other rules in Chino

All Chino rules

California rules heatmap·Compare Chino to another location·View the California building safety overview

Get notified when Fire Sprinkler Requirements in Chino, CA changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Fire Sprinkler Requirements in Nearby Cities

How other cities in San Bernardino County handle fire sprinkler requirements.

Rialto, CA
Some Restrictions
Victorville, CA
Some Restrictions
San Bernardino, CA
Significant Restrictions
Ontario, CA
Heavy Restrictions