Tempe, AZ Building Safety: Fire Sprinkler Requirements (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Mandate
Sprinklers required throughout Group R fire areas
Governing section
2024 IFC § 903.2.8 (Tempe § 14-41)
Home exception
R-3 homes/townhomes 5,000 sq ft or less
Area measured
Total under-roof area incl. garages, basements, porches
Group R-4 rule
Required for 6-10 person care facilities
Penalty
Class 1 misdemeanor, up to $2,500/90 days

Summary

Tempe's amended 2024 Fire Code requires an automatic sprinkler system throughout every Group R residential fire area, covering apartments, condos and assisted-living buildings. Detached one- and two-family homes and R-3 townhomes of 5,000 square feet or less are excepted from the mandate.

903.2.8 Group R. An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings and portions thereof with a Group R fire area. ... 903.2.8.1 Group R-3. An automatic sprinkler system installed in accordance with Section 903.3.1.3 shall be permitted in Group R-3 occupancies and their attached accessory occupancies. Exceptions: 1. R-3 occupancies and R-3 Townhome units of five thousand (5,000) square feet or less and other buildings or structures accessory to R-3 occupancies constructed in accordance with the International Building Code or the International Residential Code. The area calculation shall be based upon the total under-roof area including but not limited to basements, garages and porches etc.

View official code

Official source re-checked September 7, 2026: no newer edition of the code had been published (publisher’s edition: City Code: Supplement 33 Update 4 | Zoning and Development Code: Supplement 11 Update 2).

Full Breakdown

' Group R covers apartment buildings, condominiums, hotels, dormitories, and residential care and assisted-living facilities under the amended occupancy definitions in Chapter 2 of the same code. 1 carves out Group R-3 occupancies, single-family homes and townhome units, permitting rather than mandating sprinklers, but only for 'R-3 occupancies and R-3 Townhome units of five thousand (5,000) square feet or less,' with the area measured across the entire under-roof footprint including garages, basements and porches. A townhome or house over that 5,000-square-foot threshold loses the exception and must sprinkler like any other Group R building.

2 separately requires sprinklers throughout Group R-4 Condition 1 facilities, group homes and small assisted-living settings housing between six and ten residents receiving custodial care. 3.

Violations & Fines

Fire Code violations, including a missing or noncompliant sprinkler system, are punished under Section 113.4 as a Class 1 misdemeanor: a fine of up to $2,500, imprisonment of up to 90 days, or both, with each day the violation continues after notice from the Fire Code Official treated as a separate offense.

Frequently Asked Questions

Does my new Tempe house need a fire sprinkler system?
Only if it exceeds 5,000 square feet under roof, counting garages, basements and porches. Section 903.2.8.1 permits, rather than requires, sprinklers in Group R-3 single-family homes and townhomes at or under that size; larger homes lose the exception and must sprinkler.
Are Tempe apartment buildings required to have sprinklers?
Yes. Section 903.2.8 requires an automatic sprinkler system throughout any building containing a Group R fire area, which includes apartments, condominiums and similar multifamily occupancies. Unlike single-family homes, there is no 5,000-square-foot exception available to multifamily Group R buildings.
What is the penalty for skipping required sprinklers in Tempe?
Fire Code violations are Class 1 misdemeanors under Section 113.4, carrying a fine of up to $2,500, up to 90 days in jail, or both. Each day the sprinkler deficiency continues after the Fire Code Official's notice counts as a new, separate offense.

Sources & Official References

Other rules in Tempe

All Tempe rules

Compare Tempe to another location·View the Arizona building safety overview

Get notified when Fire Sprinkler Requirements in Tempe, AZ changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Fire Sprinkler Requirements in Nearby Cities

How other cities in Maricopa County handle fire sprinkler requirements.

Goodyear, AZ
Some Restrictions
Scottsdale, AZ
Some Restrictions
Peoria, AZ
Significant Restrictions
Chandler, AZ
Significant Restrictions
Mesa, AZ
Heavy Restrictions
Glendale, AZ
Heavy Restrictions