Goodyear, AZ Data Centers & Crypto Mining: Data Center Noise Limits (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Residential daytime limit
55 dBA at property line
Residential nighttime limit
45 dBA at property line
Industrial receiving limit
70 dBA day / 65 dBA night
Study required for
all industrial uses
Governing sections
§§ 3.11.16(C)(2)(a), 3.1.5(B)

Summary

Goodyear folds its citywide noise-threshold table into data center review: mitigation must be built into approved site and building plans before a permit issues, capping noise at a residential or noise-sensitive property line to 55 dBA by day and 45 dBA at night.

a. Noise. The Data Center shall comply with the noise standards, analysis requirements, and mitigation provisions set forth in Section 3.1.5.B of this Zoning Ordinance. Any required mitigation measures shall be incorporated into the approved site and building plans prior to issuance of a building permit. ... B. Noise which exceeds levels listed in Table 3.1.5.A Noise Thresholds when measured at or beyond the property line at the receiving property: Table 3.1.5.A Noise Thresholds, Daytime (7:00 a.m. to 10:00 p.m.) and Nighttime (10:00 p.m. to 7:00 a.m.): Industrial 70 dBA daytime, 65 dBA nighttime; Commercial 65 dBA daytime, 60 dBA nighttime; Residential or Noise-Sensitive Uses 55 dBA daytime, 45 dBA nighttime.

Full Breakdown

5(B), which caps property-line noise differently depending on the zoning of the receiving property: 70 dBA daytime / 65 dBA nighttime for an industrial receiving property, 65/60 dBA for commercial, and just 55 dBA daytime / 45 dBA nighttime for residential or other noise-sensitive receiving uses, defined to include homes, schools, churches, parks, hospitals, outdoor dining patios and hotels. 16(C)(2)(a) folds that citywide standard directly into data center review: any mitigation measures needed to meet the table must be incorporated into the approved site and building plans before the city issues a building permit, not added after the fact.

16(A)(1)) and can be demanded for a commercial use within 600 feet of residential or noise-sensitive property. A limits; the Zoning Administrator can also require a follow-up study measuring noise during peak routine operations. Combined with the section's 300-foot residential/noise-sensitive setback for the data center building and its cooling and power equipment, the noise table gives the city two separate levers, distance and decibels, to keep a data center's operational noise off neighboring residential property.

Violations & Fines

A data center that cannot demonstrate compliance with the Table 3.1.5.A thresholds, or that skips the required acoustical study, does not get its building permit: Section 3.11.16(C)(2)(a) requires mitigation measures to be incorporated into the approved site and building plans before permit issuance, not retrofitted after a noise complaint.

Frequently Asked Questions

What noise limit applies to a Goodyear data center near homes?
Table 3.1.5.A, incorporated into data center review by Section 3.11.16(C)(2)(a), caps noise measured at a residential or noise-sensitive property line to 55 dBA between 7:00 a.m. and 10:00 p.m. and 45 dBA overnight, regardless of what the data center's own industrially-zoned parcel is otherwise allowed.
Does a data center need a noise study before it can build?
Yes. Section 3.1.5 requires an initial sound study by a qualified third-party acoustical engineer for any industrial use, which covers data centers under Section 3.11.16, documenting baseline sound levels and demonstrating compliance with the Table 3.1.5.A thresholds.
When must noise mitigation be built into a data center's plans?
Before the building permit is issued. Section 3.11.16(C)(2)(a) requires any required mitigation measures to be incorporated into the approved site and building plans prior to issuance of a building permit, not added afterward.
What noise level applies if the data center's neighbor is zoned commercial?
65 dBA during the day and 60 dBA at night, per the Commercial row of Table 3.1.5.A, measured at or beyond the property line of the receiving commercial property.

Sources & Official References

Other rules in Goodyear

All Goodyear rules

Compare Goodyear to another location·View the Arizona data centers & crypto mining overview

Get notified when Data Center Noise Limits in Goodyear, AZ changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Data Center Noise Limits in Nearby Cities

How other cities in Maricopa County handle data center noise limits.

Mesa, AZ
Some Restrictions
Phoenix, AZ
Some Restrictions
Tempe, AZ
Some Restrictions
Chandler, AZ
Heavy Restrictions