Skip to main content
CityRuleLookup

Chandler, AZ Data Centers & Crypto Mining: Data Center Noise Limits (2026)

Heavy Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Standard
Not exceed ambient baseline
Generators
9am-5pm Mon-Fri only
On-site liaison
8am-10pm daily
Annual noise study
5 years post-build
Code
Sec. 35-2214(4)-(7)

Summary

Chandler sets no fixed decibel cap for data centers; instead a data center's sound may not exceed the ambient baseline noise levels measured before construction, verified by third-party acoustic engineers at the nearest residential property line. Backup generators may run only weekday daytime hours.

The Data Center must be designed and built to incorporate sound mitigation methods sufficient to prevent the sound levels emanating from the Data Center (as determined by a third-party acoustic engineer) from exceeding the ambient noise levels that were observed in the baseline study. Design specifications for such sound mitigation must be provided to the City before building permit approval.

Source: Chandler City Code ch. 35 (Zoning) - Data Center Ordinance No. 5033View official code

Full Breakdown

Under Section 35-2214, a third-party acoustic engineer must document baseline sound levels at the nearest residential (or noise-sensitive) property line before the first neighborhood meeting. The data center must be designed so its sound does not exceed that ambient baseline, with mitigation specifications submitted before building permit approval. A post-occupancy noise study is required, then repeated annually during peak mechanical operation for five years. An on-site liaison must field noise complaints daily from 8 a.m. to 10 p.m. Backup generators may operate only 9 a.m. to 5 p.m., Monday through Friday (excluding holidays), unless covering a power outage, with 24-hour public notice.

Violations & Fines

Failing the baseline sound standard, mitigation design, annual noise studies, or generator hours is a Zoning Code violation enforced by Development Services and the Zoning Administrator. An on-site liaison must respond to noise complaints daily, 8 a.m. to 10 p.m.

Frequently Asked Questions

How loud can a Chandler data center be?
There is no fixed decibel limit. The facility's sound cannot exceed the ambient baseline noise measured at the nearest residential property line before construction, verified by acoustic engineers.
When can backup generators run?
Only 9 a.m. to 5 p.m., Monday through Friday, excluding holidays, unless supplying power during an outage. Routine tests need 24-hour public and city notice.

Sources & Official References

Other rules in Chandler

All Chandler rules

Compare Chandler to another location·View the Arizona data centers & crypto mining overview

Get notified when Data Center Noise Limits in Chandler, AZ changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Data Center Noise Limits in Nearby Cities

How other cities in Maricopa County handle data center noise limits.

Mesa, AZ
Some Restrictions
Phoenix, AZ
Some Restrictions
Tempe, AZ
Some Restrictions
Goodyear, AZ
Some Restrictions