Ventura, CA Data Centers & Crypto Mining: Data Center Noise Limits (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified July 2026

Key Facts

Code
Muni Code Sec. 10.650.130
Industrial limit
70 dBA anytime
Home limit
50 day / 45 night
Commercial limit
60 dBA daytime
Measured at
Receiving property line

Summary

The City of Ventura caps noise at the receiving property line by zone under Municipal Code Sec. 10.650.130: 70 dBA anytime on industrial land, but 50 dBA daytime and 45 dBA at night at homes. Data-center cooling and generators must meet the receiver's limit.

no person shall operate or cause to be operated any source of sound ... which causes the noise level when measured on any receiving property to exceed the following noise level limits: (a) The exterior noise levels for that land use ... for a total period of more than 30 minutes in any consecutive 60 minutes

Source: City of San Buenaventura Zoning Ordinance (Title 24) & Municipal Code Ch. 10.650 Noise ControlView official code

Official source re-checked September 8, 2026: no newer edition of the code had been published (publisher’s edition: current through Ordinance 2026-008, passed May 12, 2026).

Full Breakdown

Ventura's Noise Control ordinance, Municipal Code Sec. 10.650.130, assigns each receiving property to a noise zone: Zone I noise-sensitive, Zone II residential, Zone III commercial, Zone IV industrial and agricultural. Exterior limits are Zone IV 70 dBA anytime; Zone III 60 dBA day (7 a.m.-10 p.m.) and 55 dBA night (10 p.m.-7 a.m.); Zone II 50 dBA day and 45 dBA night; Zone I 50/45. At a boundary between two zones the lower limit applies. A fixed noise source includes generators, compressors, air-conditioners and refrigeration equipment - exactly a data center's cooling and backup power. Where an industrial site abuts homes, the 45 dBA overnight residential limit binds. Short-duration exceedances above the base level are allowed on a sliding scale.

Violations & Fines

Noise over the Sec. 10.650.130 limits is a code violation enforced by the City through citations, and for a use-permitted data center it breaches the noise conditions imposed on the permit.

Frequently Asked Questions

How loud can a data center be in the City of Ventura?
On industrial land, 70 dBA at the receiving property line anytime under Municipal Code Sec. 10.650.130. Where noise reaches homes, the limit drops to 50 dBA daytime and 45 dBA overnight.
What noise rule protects homes near a Ventura data center?
The receiving property sets the limit. At a residential parcel the cap is 45 dBA from 10 p.m. to 7 a.m., so cooling and generators must be engineered to that overnight floor.

Sources & Official References

Other rules in Ventura

All Ventura rules

California rules heatmap·Compare Ventura to another location·View the California data centers & crypto mining overview

Get notified when Data Center Noise Limits in Ventura, CA changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Data Center Noise Limits in Nearby Cities

How other cities in Ventura County handle data center noise limits.

Thousand Oaks, CA
Some Restrictions
Moorpark, CA
Some Restrictions
Fillmore, CA
Some Restrictions
Port Hueneme, CA
Some Restrictions
Oxnard, CA
Some Restrictions
Camarillo, CA
Some Restrictions