Littleton, CO Environmental Rules: Flood Elevation Requirements (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Minimum freeboard
1 ft above base flood elevation
Shallow zones (A, AO, AH)
1 ft above highest adjacent grade or BFE
No mapped depth number
3 ft of freeboard required
Mechanical equipment
Elevated min. 1 ft above BFE
Manufactured homes
Elevated and anchored min. 1 ft above BFE
Applies to
New construction and substantial improvements

Summary

Littleton requires a minimum one-foot freeboard clearance between the base flood elevation and the lowest floor, including basement, of new or substantially improved structures near the floodplain, rising to three feet in shallow-flooding FEMA zones with no mapped depth number.

4. Freeboard. ... A minimum vertical clearance of one foot shall be provided between the floodplain elevations and the lowest floor (including basement) of all new or substantially improved structures within or immediately adjacent to the floodplain, and other applicable facilities which may be impacted by the floodplain freeboard is required to allow for uncertainty in the floodplain modeling, changes to the drainageway, and to provide an additional factor of safety for structures and facilities which would experience damages or hazards during inundation. ... ... 1. The lowest floor (including basement) shall be elevated to one foot above the base flood elevation; 2. Within FEMA zones A, AO, AH, or other areas of designated shallow flooding, the lowest floor (including basement), shall be elevated one foot above the highest adjacent grade, or the base flood elevation, or to the depth number specified on the FIRM, whichever is greater. Three feet of freeboard shall be provided if no depth number is specified.

Full Breakdown

E, General Construction Standards, requires all new construction and substantial improvements in or adjacent to the floodplain to be anchored against flotation and lateral movement, built with flood-resistant methods and materials, and to have electrical, heating, plumbing and HVAC equipment elevated at least one foot above the base flood elevation and protected from water intrusion. 4, Freeboard, sets the core rule: a minimum vertical clearance of one foot between the floodplain elevation and the lowest floor, including basement, of every new or substantially improved structure, added to account for uncertainty in floodplain modeling, drainageway changes, and to provide a margin of safety.

Subsection G, Residential Construction Standards, applies the same one-foot floor elevation to new residential construction, substantial improvement, and rebuilding after substantial damage, and in FEMA Zones A, AO, AH or other shallow-flooding areas requires the lowest floor to sit one foot above either the highest adjacent grade, the base flood elevation, or the FIRM's mapped depth number, whichever is greater, rising to three feet of freeboard if no depth number is mapped. Manufactured homes and their supporting utilities must likewise be elevated at least one foot above the base flood elevation and anchored against flotation, collapse and lateral movement, on top of separate state and local wind-anchoring rules. 8 authorizes this freeboard as one of the safeguards the city may impose as a condition of floodplain development approval.

Violations & Fines

Failure to meet the freeboard and elevation standards is enforced by the Floodplain Administrator within the Public Works Department, which may issue written compliance orders and pursue injunctive relief and other legal and equitable remedies under Section 10-7-1.1.B. As with other Unified Land Use Code violations, Section 10-11-2.3.A applies the General Penalty of City Code Section 1-4-1: a fine of up to $2,650 or imprisonment of up to 364 days, with each day of noncompliance a separate offense.

Frequently Asked Questions

How much freeboard does Littleton require above the base flood elevation?
At least one foot. Section 10-7-1.5.E.4 requires a minimum vertical clearance of one foot between the base flood elevation and the lowest floor, including any basement, of new or substantially improved structures in or near the floodplain.
Does Littleton require extra elevation in shallow-flooding zones?
Yes. In FEMA Zones A, AO, AH or other designated shallow-flooding areas, Section 10-7-1.5.G.2 requires the lowest floor to sit one foot above the highest adjacent grade or the base flood elevation, whichever is greater, and three feet above grade if the FIRM lists no depth number.
Do mechanical and electrical systems need to be elevated too?
Yes. Section 10-7-1.5.E.1.d requires electrical, heating, ventilation, plumbing and air conditioning equipment in new floodplain construction to be elevated at least one foot above the base flood elevation and designed to keep water out during flooding.
Are manufactured homes subject to Littleton's freeboard rule?
Yes. Section 10-7-1.5.E.2 requires manufactured homes and their supporting utilities to be elevated at least one foot above the base flood elevation and anchored against flotation, collapse and lateral movement, in addition to separate wind-anchoring requirements.

Sources & Official References

Other rules in Littleton

All Littleton rules

Compare Littleton to another location·View the Colorado environmental rules overview

Get notified when Flood Elevation Requirements in Littleton, CO changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Flood Elevation Requirements in Nearby Cities

How other cities in Arapahoe County handle flood elevation requirements.

Aurora, CO
Some Restrictions
Centennial, CO
Some Restrictions