Vermilion Parish, LA Environmental Rules: Flood Elevation Requirements (2026)
Key Facts
- Residential lowest floor
- At or above base flood elevation, basement included
- Nonresidential options
- Elevate, or floodproof watertight below base flood level
- Certification
- Engineer, architect or land surveyor to the floodplain administrator
- Enclosure openings
- Two openings, one square inch per square foot, one foot above grade
- Shallow flooding default
- At least two feet if the FIRM shows no depth number
- Manufactured home piers
- No less than 36 inches above grade in existing parks
Summary
In unincorporated Vermilion Parish, new and substantially improved residential buildings must have the lowest floor, including any basement, elevated to or above the base flood elevation, certified by an engineer, architect or land surveyor. Nonresidential buildings can elevate or be floodproofed watertight under Sec. 22-67.
In all areas of special flood hazard where base flood elevation data has been provided as set forth in section 22-7, 22-44(8), or 22-68(c), the following provisions are required: ... (1)Residential construction. New construction and substantial improvement of any residential structure shall have the lowest floor (including basement), elevated to or above the base flood elevation. A registered professional engineer, architect, or land surveyor shall submit a certification to the floodplain administrator that the standard of this subsection, as proposed in section 24-45(a)(1), is satisfied.(2)Nonresidential construction. New construction and substantial improvements of any commercial, industrial or other nonresidential structure shall either:a.Have the lowest floor (including basement) elevated to or above the base flood level; orb.Together with attendant utility and sanitary facilities, be designed so that below the base flood level the structure is watertight with walls substantially impermeable to the passage of water and with structural components having the capability of resisting hydrostatic and hydrodynamic loads and effects of buoyancy.
Full Breakdown
Sec. 22-67 of the Vermilion Parish Code sets the elevation rule wherever base flood elevation data has been provided under Sec. 22-7, 22-44(8) or 22-68(c). Sec. 22-1 defines base flood elevation as the water surface elevation shown on the FIRM and in the flood insurance study for the flood that has a one percent chance of being equaled or exceeded in any given year.
Residential construction comes first. New construction and substantial improvement of a residential structure must have the lowest floor, including a basement, elevated to or above the base flood elevation, and a registered professional engineer, architect or land surveyor must submit a certification to the floodplain administrator. Sec. 22-1 counts an improvement as substantial when its cost equals or exceeds 50 percent of the market value of the structure before construction starts.
Nonresidential buildings have two routes. The lowest floor can sit at or above the base flood level, or the structure and its utility and sanitary facilities can be designed watertight below that level, with walls substantially impermeable to water. The floodproofing route requires a registered professional engineer or architect to develop or review the design and certify it, and the floodplain administrator keeps a record of the elevation, in relation to mean sea level, to which the building is floodproofed.
Fully enclosed areas below the lowest floor usable solely for parking of vehicles, building access or storage must equalize flood forces. The default design uses a minimum of two openings on separate walls, with total net area of not less than one square inch for every square foot of enclosed area, and the bottom of every opening no higher than one foot above grade. Manufactured homes must sit with the bottom of the longitudinal I-beam at or above the base flood elevation, or in some existing parks on chassis supported by piers no less than 36 inches in height above grade.
In AO and AH shallow flooding zones, Sec. 22-69 requires the lowest floor at or above the base flood elevation or the highest adjacent grade at least as high as the depth number on the FIRM, at least two feet if no depth number is specified. Sec. 22-45(a)(1) requires every permit application to state the lowest floor elevation in relation to mean sea level. Chapter 22 does not use the word freeboard, so the printed benchmark is the base flood elevation itself.
Violations & Fines
Building below the required elevation violates Chapter 22 and is a misdemeanor under Sec. 22-72, punished as provided in Sec. 1-7: a fine not exceeding $500.00, imprisonment in the parish jail for a term not exceeding 30 days, or both. Each day the violation continues is a new violation and the violator pays the costs of the case. Only the Police Jury, sitting as appeal board under Sec. 22-46, can grant a variance below base flood elevation.
Frequently Asked Questions
How high does my floor have to be in unincorporated Vermilion Parish?
Can a commercial building be floodproofed instead of elevated?
What counts as a substantial improvement?
What is the rule for shallow flooding zones?