Springfield, IL Fire Regulations: Propane Storage (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Trigger
Above-ground meters/tanks near alleys, driveways, parking
Bollard size
Min. 4-inch steel pipe filled with concrete
Height
Min. 36 in. above grade, 36 in. below grade
Spacing
Posts no more than 4 ft on center
Clearance
Min. 36 in. from the meter or equipment
Code basis
2018 IFC Section 312

Summary

Springfield doesn't cap how much propane a resident can store, but Sec. 94.65 does require physical protection for above-ground LPG and natural gas installations exposed to vehicle traffic: bollards or posts around meters, regulators, piping and tanks near alleys, driveways or parking areas, sized to the 2018 International Fire Code's Section 312 standard.

When exposed to probable vehicular damage due to proximity to alleys, driveways, or parking areas, above-ground gas meters, regulators, piping and tanks for LPG and natural gas installations shall be suitably protected as follows as outlined in 2018 IFC section 312:(1)Posts or bollards shall be a minimum of four-inch steel pipe filled with concrete or be of a material of equivalent strength.(2)Posts or bollards shall be a minimum of 36 inches in height.(3)Posts or bollards shall extend a minimum of 36 inches below grade and be set in a concrete footing.(4)Protection shall be provided on all sides of the object that is subject to vehicular damage.(5)Posts or bollards shall be a minimum of 36 inches away from gas meters and other essential equipment.(6)Posts shall be set not more than four feet on center between posts. Any equivalent measure or deviation from this policy shall require approval from the fire safety division.

View official code

Official source re-checked September 7, 2026: no newer edition of the code had been published (publisher’s edition: Code of Ordinances: Supplement 82).

Full Breakdown

Sec. 65 kicks in whenever above-ground gas meters, regulators, piping, or tanks for LPG or natural gas installations are exposed to probable vehicular damage because of their proximity to alleys, driveways, or parking areas. In those cases the code requires suitable protection under the 2018 International Fire Code, Section 312: posts or bollards made of at least four-inch steel pipe filled with concrete, or material of equivalent strength, standing a minimum of 36 inches above grade and extending at least another 36 inches below grade in a concrete footing.

Protection has to be provided on every side of the equipment that's exposed to vehicular damage, the posts or bollards must sit at least 36 inches away from the meters and other essential equipment, and individual posts can't be spaced more than four feet apart on center. The section closes with a safety valve for property owners: any equivalent protection measure, or any deviation from this specific bollard layout, needs prior approval from the fire safety division before it satisfies the rule. The provision sits in Article VI alongside Sec.

64's above-ground flammable liquid tank permitting and Sec. 66's ten-foot clearance for combustible storage near egress doors, all administered by the same Fire Safety Division review process.

Violations & Fines

Above-ground gas meters, regulators, piping, or LPG/natural gas tanks near an alley, driveway, or parking area that lack the required bollards, or whose bollards fall short of the four-inch, 36-inch-above/36-inch-below-grade spec in Sec. 94.65, are out of compliance with the Fire Safety Division's inspection standard; any alternative protection method needs the division's prior approval to be lawful.

Frequently Asked Questions

Does Springfield cap how much propane I can store at home?
The city's fire code doesn't set a residential storage-volume limit in Sec. 94.65; instead it requires physical protection, bollards or posts, around above-ground LPG and gas installations that sit close to vehicle traffic like alleys, driveways, or parking areas.
What size bollards does the code require?
Sec. 94.65 calls for posts or bollards at least four inches of steel pipe filled with concrete (or equal strength), standing a minimum of 36 inches above grade, set at least 36 inches below grade in a concrete footing, and spaced no more than four feet apart on center.
Can I use a different protection method?
Only with sign-off. Sec. 94.65 states any equivalent measure or deviation from the listed bollard specifications requires approval from the fire safety division before it satisfies the rule.

Sources & Official References

Other rules in Springfield

All Springfield rules

Compare Springfield to another location·View the Illinois fire regulations overview