Ventura, CA Fire Regulations: Propane Storage (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Applies in
Mapped High/Very High Fire Hazard Severity Zones
Bare soil clearance
10 feet around tank
Vegetation buffer
Additional 10 feet, no flammable growth
State cross-reference
14 CCR § 1299.03(c)(1)
Enforcement
Fire code official, Ch. 8.10 abatement

Summary

In High and Very High Fire Hazard Severity Zones within the City of Ventura, Appendix Section J105.3 of the wildland-urban interface code amendments requires outbuildings and liquid propane gas storage tanks to keep 10 feet of clearance to bare mineral soil, plus an additional 10 feet free of flammable vegetation around their exterior.

F105.3 Other Requirements. A. Logs/Stumps. Logs or stumps embedded in the soil must be removed or isolated from other vegetation. B. Out Buildings/LPG. Outbuildings and Liquid Propane Gas (LPG) storage tanks shall have 10 feet of clearance to bare mineral soil and no flammable vegetation for an additional 10 feet around their exterior, pursuant to 14 CCR Section 1299.03(c)(1).

View official code

Official source re-checked September 8, 2026: no newer edition of the code had been published (publisher’s edition: current through Ordinance 2026-008, passed May 12, 2026).

Full Breakdown

165 by Ordinance No. 3). 03(c)(1). 1 designates as High or Very High Fire Hazard Severity Zones on the city's adopted CAL FIRE map, not citywide; a propane tank outside a mapped fire hazard severity zone is not covered by this appendix. The same appendix section pairs the propane clearance rule with two neighboring outbuilding duties: address numbers must be displayed in contrasting colors and readable from the street, and chimney or stovepipe openings need spark arrester screens with openings between three-eighths and one-half inch. 10 timeframes described in Section J106.

Violations & Fines

A propane or LPG storage tank within a mapped High or Very High Fire Hazard Severity Zone that lacks the required 10-foot bare-mineral-soil clearance and 10-foot flammable-vegetation buffer can be cited by the fire code official as part of the Appendix J fire-hazard-abatement process, with the parcel subject to a written correction order and the abatement timeframes in Chapter 8.10 of the municipal code.

Frequently Asked Questions

Does Ventura regulate how close a propane tank can be to vegetation?
Yes, but only within the city's mapped High and Very High Fire Hazard Severity Zones. Appendix Section J105.3(B) of the wildland-urban interface amendments requires 10 feet of clearance to bare mineral soil around an LPG storage tank plus an additional 10 feet free of flammable vegetation.
Is my propane tank covered if I'm not in a fire hazard zone?
No. The 10-foot clearance rule in Appendix Section J105.3(B) is part of the Wildland-Urban Interface Code amendments in Chapter 12.165, which apply only to land the city has mapped as High or Very High Fire Hazard Severity Zone under Section 302.2.1.
What happens if my propane tank doesn't have the required clearance?
The fire code official can address a noncompliant clearance through the Appendix J fire-hazard-abatement process, which starts with a written order and runs on the timeframes in Chapter 8.10 of the San Buenaventura Municipal Code, the same procedure used for other WUI vegetation violations.

Sources & Official References

Other rules in Ventura

All Ventura rules

California rules heatmap·Compare Ventura to another location·View the California fire regulations overview