Sherman, TX Building Safety: Carbon Monoxide Detectors (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified October 2026

Key Facts

Code section
Sherman Code of Ordinances § 3.04.001(a)(60), IFC 907.2.8.4
Triggers
Underground garage, vehicle storage area, or parking within the structure
System type
Approved, monitored, and tied to the fire alarm panel
Exception
Group R-3
Fire code adopted
2021 International Fire Code with local amendments
Enforcer
Sherman Fire Marshal's Office
Penalty path
Section 1.01.009, up to $2,000.00 for fire safety rules

Summary

In the City of Sherman, Texas, the Fire Code amendment at Sherman Code of Ordinances § 3.04.001(a)(60) adds section 907.2.8.4. An approved carbon monoxide detection system must be installed and maintained in every building with an underground garage or vehicle storage area, and in buildings that provide parking as part of the structure. The system is monitored and reports through the fire alarm panel. Group R-3 is excepted.

Section 907.2.8.4 is hereby added to read as follows: 907.2.8.4 Carbon monoxide detectors. An approved carbon monoxide detection system shall be installed and maintained in all buildings that include an underground garage or vehicle storage area and in buildings that provide parking as part of the structure. The detection system shall be monitored and shall signal an alarm as part of the fire alarm panel. Exception: (A) Group R-3.

Full Breakdown

Sherman's carbon monoxide rule lives in the fire code, not in a stand-alone detector ordinance. Section 3.03.008 points readers to article 3.04, and § 3.04.001(a) adopts the 2021 edition of the International Fire Code as the fire prevention code of the City of Sherman, Texas, followed by a numbered list of local additions, amendments and deletions. Item (60) in that list adds section 907.2.8.4, titled Carbon monoxide detectors.

The trigger is the building, not the occupant. Any building that includes an underground garage or vehicle storage area needs an approved carbon monoxide detection system, and so does any building that provides parking as part of the structure. The code says the system must be installed and also maintained, so the duty continues after the final inspection. The detection system must be monitored and must signal an alarm as part of the fire alarm panel, which means a stand-alone battery unit in a parking level does not satisfy the text.

The only exception printed under the section is Group R-3.

The neighboring amendments shape how the system gets built. Section 907.1.4 requires new or replacement alarm systems to be analog intelligent addressable fire detection systems, and section 907.6.3.2 says that when a fire alarm system is required by that section or by the fire code official, the system shall be point addressable and must send type and location information to Sherman Fire-Rescue dispatch. Section 103.1 creates the Sherman Fire Marshal's Office, headed by the fire code official, to implement and enforce the code. Article 3.04 was last amended by Ordinance 6691 adopted 2/5/2024 and Ordinance 6939 adopted 6/1/2026.

Violations & Fines

Section 3.04.001(b) provides that violations of any provision of article 3.04 are punishable as provided in Section 1.01.009 of the Code. That general penalty section sets a fine not exceeding $500.00, and states that a fine for violating a rule that governs fire safety, zoning or public health and sanitation cannot exceed $2,000.00. Enforcement runs through the Sherman Fire Marshal's Office.

Frequently Asked Questions

Which buildings in the City of Sherman, Texas need a carbon monoxide detection system?
Section 907.2.8.4, added by § 3.04.001(a)(60), applies to all buildings that include an underground garage or vehicle storage area and to buildings that provide parking as part of the structure. The system must be approved, installed, maintained, monitored, and wired to signal as part of the fire alarm panel.
Does this section cover carbon monoxide alarms in single-family homes?
The printed exception under section 907.2.8.4 is Group R-3, and the section itself speaks only to garages, vehicle storage areas and structured parking. The phrase carbon monoxide appears nowhere else in the Sherman Code of Ordinances text, so household alarm requirements are not addressed in this section.
Who enforces the rule in Sherman?
Section 103.1, as amended, creates the Sherman Fire Marshal's Office and names its head the fire code official. The fire chief appoints the fire marshal under section 103.2. That office implements, administers and enforces the fire code, including the carbon monoxide amendment.
What is the fine for violating the fire code amendments?
Section 3.04.001(b) sends violations to Section 1.01.009. That section sets a fine not exceeding $500.00 where no specific penalty exists, but caps fines for fire safety, zoning or public health rules at $2,000.00, and counts each day of a continuing violation separately.

Sources & Official References

Other rules in Sherman

All Sherman rules

Texas rules heatmap·Compare Sherman to another location·View the Texas building safety overview

Get notified when Carbon Monoxide Detectors in Sherman, TX changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.