Data Centers & Crypto Mining in Irving, TX (2026)

3 verified data centers & crypto mining rules for Irving, Texas, sourced directly from the municipal code and official government pages.

Verified from official government sources

Data Center Zoning & Siting

In Irving, a data center is a principal use allowed only by Conditional Use Permit, and only in the C-W, ML-20, ML-20a, ML-40, ML-120, or C-P districts. Smaller accessory data centers are permitted in five office and commercial districts.

Irving Data Center Zoning and Siting Rules

Significant Restrictions

Irving Unified Development Code Sec. 3.20.1(c), Data Center Standards (Ord. 2025-11063, adopted Feb. 6, 2025)

3.20.1 Applicability. ... c) New data centers shall be permitted as a principal use by Conditional Use Permit (CUP) only. An application for a CUP shall only be made within the C-W, ML-20, ML-20a, ML-40, ML-120, or C-P districts.

Data Center Noise Limits

Irving's noise code singles out standby generators at data centers: they cannot be tested or run for maintenance between 7:00 p.m. and 7:59 a.m., and are expressly excluded from the 85 dBA allowance that covers residential mechanical equipment.

Irving Data-Center Standby Generator Noise Rules

Some Restrictions

Irving City Code § 22-3(a)(14) (Noise — Standby power generators); Ord. 2024-11013, adopted 10/3/2024

(14) Standby power generators. Generators must be installed and operated only in accordance with manufacturer's specifications and in accordance with permitting standards and approvals as established by the city's inspection department. Additionally, for the purposes of this code, standby generators (including those at data centers or other commercial/industrial properties) are not considered "...

Crypto Mining Rules

Irving has no cryptocurrency-specific ordinance. A crypto-mining operation is classified as a 'data center' under the Unified Development Code: a defined principal use allowed only in appropriate nonresidential districts and expressly prohibited in the Heavy Industrial Mixed-Use (HI-MU) district.

Irving Crypto Mining Rules (Data Center Zoning)

Some Restrictions

Irving Unified Development Code § 9.3, Definitions — 'Data center — principal use'

Data center - principal use shall mean an establishment engaged in the storage, management, processing, and/or transmission of digital data, which houses computer and/or network equipment, systems, servers, appliances and other associated components related to digital data operations.

Looking for Dallas County county-wide rules?

County ordinances apply to unincorporated areas and may supplement Irving city rules.

Data Centers & Crypto Mining in Dallas County