Pacifica, CA Environmental Rules: Flood Elevation Requirements (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

AE/AH/A1-30 zones
Lowest floor at or above BFE
AO zone default
2 feet above highest adjacent grade
Certification required from
Registered civil engineer or land surveyor
Verified by
City Building Official
Nonresidential alternative
Dry floodproofing to watertight standard

Summary

New and substantially improved residential structures in Pacifica's special flood hazard areas must have their lowest floor, including any basement, elevated to or above the base flood elevation shown on FEMA's maps. In an AO zone without a mapped depth, the lowest floor must sit at least two feet above the highest adjacent grade, and elevation must be certified by a registered engineer or surveyor.

In all special flood hazard areas, the following standards are required: ... Elevation and floodproofing.(1)Residential construction. All new construction or substantial improvements of residential structures shall have the lowest floor, including basement:(i)In AE, AH, A1-30 Zones, elevated to or above the base flood elevation.(ii)In an AO Zone, elevated above the highest adjacent grade to a height equal to or exceeding the depth number specified in feet on the FIRM, or elevated at least two (2) feet above the highest adjacent grade if no depth number is specified.

Full Breakdown

501(c) sets the elevation and floodproofing standards that apply throughout the City's special flood hazard areas. For residential construction, all new construction or substantial improvements must have the lowest floor, including any basement, elevated to or above the base flood elevation in Zones AE, AH and A1-30. 402(c). Once construction is complete, a registered civil engineer or licensed land surveyor must certify the elevation of the lowest floor, and the City's Building Official verifies that the structure was properly elevated before that certification and verification go to the Floodplain Administrator.

Nonresidential structures have an alternative: instead of elevating to the same height, they can be floodproofed so the structure is watertight, with walls substantially impermeable to water and structural components able to resist hydrostatic and hydrodynamic loads, certified by a registered civil engineer or architect. Enclosed areas below the lowest floor that are used only for parking, building access or storage must have flood vents, at least two openings on different walls providing one square inch of net area per square foot of enclosed area, with the bottom of each opening no higher than one foot above grade, so hydrostatic pressure equalizes automatically during flooding.

Violations & Fines

Occupying or altering a structure that doesn't meet the Section 7-5.501 elevation and floodproofing standards is a misdemeanor under Section 7-5.303, chargeable as an infraction at the City Attorney's discretion. A structure lacking the required elevation certificate is presumed to be in violation under the chapter's definitions until the property owner produces that documentation to the Floodplain Administrator.

Frequently Asked Questions

How high above the base flood elevation must a new Pacifica home be built?
Section 7-5.501(c)(1) requires the lowest floor, including any basement, to be elevated to or above the base flood elevation in AE, AH and A1-30 zones; the code doesn't set a freeboard margin above that line for those zones.
What if my lot is in an AO zone with no depth number on the map?
Section 7-5.501(c)(1)(ii) requires the lowest floor to be elevated at least two feet above the highest adjacent grade when the Flood Insurance Rate Map doesn't specify a depth number for the AO zone.
Who has to certify my home's flood elevation?
A registered civil engineer or licensed land surveyor must certify the lowest floor elevation once construction is finished, and the City's Building Official verifies the structure was properly elevated before that documentation goes to the Floodplain Administrator under Section 7-5.501(c)(1).

Sources & Official References

Other rules in Pacifica

All Pacifica rules

California rules heatmap·Compare Pacifica to another location·View the California environmental rules overview

Get notified when Flood Elevation Requirements in Pacifica, CA changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Flood Elevation Requirements in Nearby Cities

How other cities in San Mateo County handle flood elevation requirements.

Redwood City, CA
Some Restrictions