Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Construction permit threshold
125 gallons per container, IFC § 105.6.16
Operational permit threshold
125 gallons, IFC § 105.5.30(1)
Citywide aggregate cap
2,000 gallons water capacity, IFC § 6104.2
Permitting agency
North Metro Fire Rescue District
Maintenance rule
Routine maintenance is not a modification
Max penalty
$2,650 fine or 364 days jail

Summary

Broomfield's Fire Code sets a 125-gallon threshold before a residential LP-gas container needs a construction permit, and caps the aggregate water capacity of any one installation citywide at 2,000 gallons, per Broomfield Municipal Code § 15-16-010(J) and (ZZ).

105.6.16 LP-Gas. ... A construction permit is required for the installation or modification to an LP-gas system incorporating an individual container that exceeds a 125-gallon (474 L) water capacity. Maintenance performed in accordance with this code is not considered to be a modification and does not require a permit. ... 6104.2 Maximum capacity within established limits. ... Within the City and County of Broomfield, the aggregate capacity of any one installation shall not exceed a water capacity of 2,000 gallons (7570 L).

Full Breakdown

Chapter 15-16 of the Broomfield Municipal Code amends the 2024 International Fire Code's LP-gas provisions for the City and County of Broomfield. Subsection 105.6.16 requires a construction permit before anyone installs or modifies an LP-gas system that includes an individual container exceeding 125 gallons of water capacity; routine maintenance that is not a modification does not trigger the permit. A separate operational-permit trigger appears at Subsection 105.5.30(1), which lists storage and use of LP-gas exceeding 125 gallons water capacity among the activities North Metro Fire Rescue District must permit before they begin.

On top of the per-container threshold, Subsection 6104.2 sets a citywide ceiling: within the City and County of Broomfield, the aggregate capacity of any one installation, meaning every LP-gas container on that site added together, cannot exceed a water capacity of 2,000 gallons. A homeowner with a single small cylinder for a grill or fire pit stays under both thresholds and needs no permit, but a property owner adding a bulk tank, or several tanks that together exceed 125 or 2,000 gallons, must apply to the fire code official before the tank is installed or filled.

North Metro Fire Rescue District reviews and issues both the construction and operational permits and can inspect an installation to confirm the container count and aggregate capacity match what was permitted. Appeals of a permit denial go first to the fire chief and then to the Board of Adjustment under IFC Section 112.

Violations & Fines

Installing, modifying, storing, or using LP-gas without the required construction or operational permit, exceeding the 125-gallon per-container threshold in IFC § 105.6.16, or exceeding the 2,000-gallon aggregate capacity limit in IFC § 6104.2, violates Broomfield Municipal Code § 15-16-010. The fire code's general penalty at B.M.C. Chapter 1-12 applies: a fine up to $2,650.00, imprisonment up to 364 days, or both, with each day the violation continues counted as a separate offense.

Frequently Asked Questions

Does Broomfield require a permit to install a propane tank at home?
Only above certain sizes. Broomfield Municipal Code § 15-16-010(J), amending IFC Section 105.6.16, requires a construction permit for any LP-gas system with an individual container over 125 gallons of water capacity; smaller cylinders used for grills or fire pits do not need one.
Is there a limit on how much propane one property can store in Broomfield?
Yes. IFC Section 6104.2, as amended by Broomfield Municipal Code § 15-16-010(ZZ), caps the aggregate water capacity of every LP-gas container at a single installation at 2,000 gallons within the City and County of Broomfield, regardless of how many tanks make up that total.
Who issues Broomfield's LP-gas permits and inspects propane installations?
North Metro Fire Rescue District, acting as the fire code official under Broomfield Municipal Code Chapter 15-16, issues both the construction and operational LP-gas permits and can inspect a site to confirm the installed containers do not exceed the permitted capacity.

Sources & Official References

Other rules in Broomfield

All Broomfield rules

Compare Broomfield to another location·View the Colorado fire regulations overview

Get notified when Propane Storage in Broomfield, CO changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.