Key Facts

Highest-tier device
Air gap separator (potable supplements recycled)
Mid-tier device
Reduced pressure principle assembly
Lightest-tier device
Double check valve, dual-plumbed irrigation
Testing frequency
At least annually
Defect correction window
3 days
Enforcement
Water service denial or discontinuance

Summary

Any Lynwood property that receives recycled water alongside city drinking water needs backflow protection sized to the connection under Lynwood Municipal Code § 14-1.66(c). The strictest device, an air gap separator, is required wherever recycled water supplements the potable supply.

c. Recycled Water: 1. Minimum protection: air gap separation (AG) backflow prevention device. Premises where the public water system is used to supplement the recycled water supply. 2. Minimum protection: reduced pressure principle (RP) backflow prevention device. Premises where recycled water is used other than as allowed in subsection 14-1.66c3, and there is no interconnection with the potable water system. 3. Minimum protection: double check valve assembly (DC) backflow prevention device. Residences using recycled water for landscape irrigation as part of an approved dual plumbed-use area.

Full Breakdown

Lynwood folds recycled water into its general cross-connection control program rather than writing a separate recycled-water ordinance. Section 14-1.66 sets the minimum backflow device required at a connection based on the hazard involved, and subsection (c) addresses recycled water specifically in three tiers. Where the city's potable water system is used to supplement a recycled water supply, the property needs the highest level of protection, an air gap separation (AG) device, which under § 14-1.63(a) must be built at least double the diameter of the supply pipe and never less than one inch, measured vertically from the flood rim of the receiving vessel to the supply pipe. Where recycled water is used but is not interconnected with the potable system, a reduced pressure principle (RP) device is the minimum under § 14-1.66(c)(2). Residences using recycled water for landscape irrigation through an approved dual-plumbed system need only the lightest protection, a double check valve assembly (DC), under § 14-1.66(c)(3).

Whichever device applies, § 14-1.64 puts the public works department or city engineer in charge of determining the specific type, design and layout required at each premises, at the customer's expense, and installation is a condition of receiving water service at all. Section 14-1.69 then requires the device to be tested at least annually, or more often if the health agency or city decides it is necessary, by a tester who has demonstrated competency to the city, with any defect corrected within three days of discovery. A property that skips a required recycled-water backflow device, or lets one go untested, faces the same enforcement the rest of the cross-connection program uses.

Violations & Fines

Section 14-1.70 lets Lynwood deny or discontinue water service, after reasonable notice, to any premises where a required backflow device for recycled water is missing, has been removed or bypassed, or has not been tested, maintained and repaired to the city's satisfaction. Service is not restored until the customer fixes the deficiency and pays the required reconnection fee, and the customer bears the cost of any contamination cleanup caused by the failure.

Frequently Asked Questions

What backflow device does Lynwood require for recycled water?
Lynwood ties the device to how the recycled water connects. Section 14-1.66(c) requires the strongest device, an air gap separator, wherever potable water supplements a recycled water supply; a reduced pressure principle device where recycled water has no interconnection with the potable system; and a double check valve for approved dual-plumbed residential irrigation.
How often must a recycled-water backflow device be tested in Lynwood?
At least once a year, or more often if the health agency or the city decides it is necessary, under § 14-1.69. The test must be performed by someone who has demonstrated competency to the city, and any defect found must be corrected within three days.
What happens if a Lynwood property doesn't install the required recycled-water backflow device?
The city can deny or discontinue water service to the premises under § 14-1.70. Service isn't restored until the missing or defective device is corrected to the city's satisfaction and the customer pays any required reconnection fee, plus cleanup costs from any resulting contamination.

Sources & Official References

Other rules in Lynwood

All Lynwood rules

California rules heatmap·Compare Lynwood to another location·View the California water use rules overview

Get notified when Recycled Water Rules in Lynwood, CA changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Recycled Water Rules in Nearby Cities

How other cities in Los Angeles County handle recycled water rules.

West Covina, CA
Light Restrictions
Carson, CA
Light Restrictions
El Monte, CA
Some Restrictions
Norwalk, CA
Some Restrictions
Santa Clarita, CA
Some Restrictions
Glendale, CA
Some Restrictions
Pasadena, CA
Some Restrictions
Lancaster, CA
Some Restrictions