Key Facts

Adopted code
2017 National Electrical Code, § 7-05-005
Administration
Article 7-01, enforced through the building official, § 7-05-007
Existing wiring
Additions or alterations first approved by building official, § 7-05-010
Tamper-resistant receptacles
Not required in detached one and two-family dwelling units
Panels
Separate distribution panel for each store, apartment or dwelling
Criminal penalty
Class 1 misdemeanor, fine up to $2,500, up to six months

Summary

In the Town of Prescott Valley, Arizona, all electrical work must follow the 2017 National Electrical Code as amended by Town Code Article 7-05, plus the rules set by the building official. Section 7-05-005 adopts the NEC and § 7-05-007 routes administration and enforcement to Article 7-01. Permits come from the building official under § 7-01-140.

The National Electrical Code (NEC), 2017 Edition, as copyrighted by the National Fire Protection Association, Inc., with amendments contained in this document, is hereby adopted by reference as though fully set forth herein, as one of the technical codes of the Town of Prescott Valley. At least three (3) copies of the aforesaid NEC shall be filed in the Office of the Town Clerk and made available for public use and inspection. ... Any and all electrical work for light, heat, power or any other purpose shall be installed in conformity with the rules and regulations as set forth in that document titled the National Electrical Code, 2017 Edition, as amended herein, and in conformity with the rules and regulations set forth by the building official. ... This National Electrical Code shall be administered and enforced pursuant to Article 7-01, THE TOWN OF PRESCOTT VALLEY ADMINISTRATIVE CODE, in Chapter 7, BUILDING, of the Prescott Valley Town Code.

Full Breakdown

Section 7-05-005 adopts the National Electrical Code (NEC), 2017 Edition, "as one of the technical codes of the Town of Prescott Valley," with at least three copies on file in the Office of the Town Clerk for public inspection. Section 7-05-007 adds to NEC Article 90 that all electrical work for light, heat, power or any other purpose must conform to the 2017 NEC as amended and to the rules set by the building official, and that the code is administered and enforced under Article 7-01 of the Town Code.

The Town then amends specific NEC provisions. Section 7-05-010 rewrites NEC 110.8 so that, for existing or relocated buildings, the NEC applies where the building official deems the wiring methods inadequate or unsafe; relocated buildings must have service equipment that conforms to NEC Article 230; and additions to or alterations in existing wiring must first be approved by the building official. Section 7-05-040 deletes NEC 406.4(D)(5), adds an exception to 406.12 so tamper-resistant receptacles are not required in detached one and two-family dwelling units, and adds to NEC 408.30 a rule that each separate store, apartment or dwelling has its own lighting and power distribution panels, while hotels, motels and similar buildings can be wired from one or more distribution panels.

Permits sit in § 7-01-140. Subsection (F) lists the electrical work that needs no electrical permit, such as portable motors with an attachment plug, listed cord and plug temporary decorative lighting, repair or replacement of an overcurrent device of the required capacity in the same location, and wiring operating at less than 25 volts that cannot supply more than 50 watts. Work exempt from a building permit still needs a separate electrical permit unless otherwise exempted. Applications follow § 7-01-150, and work must stay exposed for inspection under § 7-01-180, where the building official can require that an inspection request be filed at least one working day ahead, including through the Selectron Inspection Request System.

Violations & Fines

Violating any provision of Chapter 7 of the Town Code is a class 1 misdemeanor under § 7-01-130(A), punishable by a fine not to exceed $2,500, imprisonment not to exceed six months, or both, and each day is a separate offense. The civil route in § 7-01-130(B) carries a sanction not to exceed $250 per citation under Article 1-08. Paying a penalty does not relieve the violator of correcting the work, and the Town can seek an injunction or abatement.

Frequently Asked Questions

Which edition of the NEC does Prescott Valley enforce?
The 2017 Edition, copyrighted by the National Fire Protection Association, Inc., as amended by Town Code Article 7-05. Section 7-05-005 adopts it by reference as one of the technical codes of the Town of Prescott Valley, with copies on file in the Office of the Town Clerk.
Can I add a circuit to existing wiring without approval?
No. NEC 110.8 as amended by § 7-05-010 says additions to, or alterations in, existing wiring must first be approved by the building official. The NEC also applies to existing or relocated buildings when the building official deems the wiring methods inadequate or unsafe.
Does replacing a receptacle need an electrical permit?
Section 7-01-140(F)(5) exempts reinstallation of attachment plug receptacles, but not the outlets thereof, from the electrical permit requirement. Anything beyond that list, including new circuits or outlets, falls under the permit requirement in § 7-01-140(A), which is separate from any zoning approval.
Are tamper-resistant receptacles required in new houses?
Section 7-05-040 deletes NEC 406.4(D)(5) and adds an exception to NEC 406.12 stating that the tamper-resistant receptacle subsection does not apply to detached one and two-family dwelling units. The exception is limited to those units, so the standard NEC wording still governs other buildings.
How do I request an electrical inspection?
The permit holder notifies the building official that work is ready, and the building official can require each request at least one working day before the inspection is desired. Requests can be made in writing, by telephone through the Selectron Inspection Request System, or another approved method, and work stays exposed until approved.

Sources & Official References

Other rules in Prescott Valley

All Prescott Valley rules

Compare Prescott Valley to another location·View the Arizona building safety overview

Get notified when Electrical Permits in Prescott Valley, AZ changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Electrical Permits in Nearby Cities

How other cities in Yavapai County handle electrical permits.

Sedona, AZ
Some Restrictions