Jackson, TN Building Safety: Fire Sprinkler Requirements (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Applies to
Group R-2 apartments up to 5 stories
Sprinkler requirement
Throughout, per § 903.3.1.1 (§ 12-204)
Sprinkler type
Residential-type in every dwelling unit
Density limit
Max 4 dwelling units per floor
Travel distance
125-foot maximum to exit stairway
Adopted
Ordinance #2025-15, January 2025

Summary

Jackson Municipal Code § 12-204, adopted by Ordinance #2025-15 in January 2025, amends the 2018 International Building Code's Section 1006.3.3 so that a Group R-2 apartment building of up to five stories served by a single exit stairway must be sprinklered throughout, with residential-type sprinklers in every dwelling unit's habitable spaces.

Section 1006.3.3 of the 2018 Edition of the International Building Code is hereby amended by adding a new condition 6 as follows: 6.Not more than five stories of Group R-2 Occupancy are permitted to be served by a single exit under the following conditions:6.1The building has not more than six stories above grade plane. ... 6.4.The building shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. Residential-type sprinklers shall be used in all habitable spaces in each dwelling unit.

Full Breakdown

Section 12-204 of the Jackson Municipal Code, added by Ordinance #2025-15 in January 2025, creates a new "Condition 6" inside Section 1006.3.3 of the locally adopted 2018 International Building Code, governing when a Group R-2 apartment building, meaning multifamily residential occupancy, may rely on a single exit stairway instead of the two exits the IBC generally requires. Condition 6 allows up to five stories of Group R-2 occupancy on a single exit only if the building is no taller than six stories above grade, is not a boarding house or used for transient occupants, and has no more than four dwelling units per floor.

Critically for fire protection, subsection 6.4 mandates that the building be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, and further specifies that residential-type sprinklers be used in all habitable spaces in each dwelling unit, making sprinkler coverage a non-negotiable trade-off for the single-stair design. The amendment pairs the sprinkler mandate with other life-safety conditions: a maximum of two single-exit-stairway conditions per property separated by two-hour fire-rated walls, a pressurized interior exit stairway, self-closing sixty-minute fire-rated dwelling unit doors, a travel distance cap of 125 feet to the exit, and restrictions on what other occupancies may share the building.

Compliance is reviewed by the Building and Housing Codes Department established under § 12-102 as part of plan review and inspection for any qualifying apartment project.

Violations & Fines

Because § 12-204 operates inside the adopted 2018 International Building Code, a building that uses the single-exit-stairway allowance without meeting every Condition 6 requirement, including the automatic sprinkler system in Section 903.3.1.1, fails building code plan review by the Building and Housing Codes Department and cannot receive a certificate of occupancy; unresolved violations otherwise fall to the general penalty provision, § 3-102, up to five hundred dollars ($500.00) plus costs.

Frequently Asked Questions

Does Jackson require sprinklers in apartment buildings?
Only apartment buildings that use the single-exit-stairway allowance created by § 12-204 must be sprinklered throughout: Condition 6.4 requires an automatic sprinkler system built to Section 903.3.1.1 plus residential-type sprinklers in every habitable space of every dwelling unit as the trade-off for skipping a second exit.
How tall can a single-exit apartment building be in Jackson, TN?
Section 12-204's Condition 6 caps it at five stories of Group R-2 occupancy inside a building no more than six stories above grade, with no more than four dwelling units per floor and a maximum 125-foot travel distance to the exit stairway.
When did Jackson add this sprinkler condition to its building code?
The city council added Condition 6 to Section 1006.3.3 of the locally adopted 2018 International Building Code through Jackson Municipal Code § 12-204, enacted by Ordinance #2025-15 in January 2025, and it applies going forward to any Group R-2 apartment project seeking to use a single exit stairway design under that condition.

Sources & Official References

Other rules in Jackson

All Jackson rules

Compare Jackson to another location·View the Tennessee building safety overview

Get notified when Fire Sprinkler Requirements in Jackson, TN changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.