Bossier Parish, LA Environmental Rules: Flood Elevation Requirements (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Freeboard
1 foot above base flood elevation, residential
Red River map areas
18 inches above advisory BFE instead
Certification
Registered engineer, architect, or land surveyor required
Penalty
Up to $100 fine or 5 days jail per day
Governing section
Bossier Parish Code § 54-92

Summary

New or substantially improved residential structures in a Bossier Parish special flood hazard area must have their lowest floor, plus mechanical and electrical equipment, raised at least one foot above the base flood elevation under Code § 54-92(1), certified by a registered engineer, architect, or land surveyor.

These county ordinances apply to unincorporated areas of Bossier Parish. Incorporated cities within the county may have their own rules that take precedence over county-level regulations.

(1)Residential construction. New construction and substantial improvement of any residential structure shall have the lowest floor (including basement), mechanical and electrical equipment and duct work elevated to a minimum of one foot above the base flood elevation. A registered professional engineer, architect, or land surveyor shall submit a certification to the floodplain administrator that the standard of this subsection as proposed in division 4, section 54-73(1)a., is satisfied.

Full Breakdown

Bossier Parish Code § 54-92 sets the specific elevation standards that apply once base flood elevation data exists for a site, whether from the FEMA Flood Insurance Study adopted at § 54-52, the floodplain administrator's own data under § 54-72(8), or subdivision-generated data under § 54-93(3). For residential construction, § 54-92(1) requires the lowest floor, including any basement, plus all mechanical and electrical equipment and duct work, to sit at least one foot above the base flood elevation; a registered professional engineer, architect, or land surveyor must certify to the floodplain administrator that the structure meets that standard as part of the permit application required under § 54-73(1)a.

Nonresidential structures get an alternative under § 54-92(2): they can either meet the same one-foot freeboard or be floodproofed watertight below that line, with an engineer's certification kept on file recording the specific elevation to which the structure was floodproofed. Section 54-92(6) raises the bar further wherever the Red River Advisory Base Flood Elevation Map, dated January 4, 2016, supersedes the FEMA FIRM panels: in that area, the required elevation becomes 18 inches above the Red River Advisory map's base flood elevation instead of the standard one foot above the FIRM's base flood elevation.

Violations & Fines

Building or substantially improving a structure without meeting the § 54-92 elevation standard, or without the engineer's or architect's certification the section requires, is a violation of Chapter 54's flood damage prevention article under § 54-97: a misdemeanor punishable by a fine of up to $100.00 or up to five days in jail, or both, with each day the violation continues counted as a separate offense, plus all costs and expenses of the case.

Frequently Asked Questions

How high above flood level must a new house be built in Bossier Parish?
Code § 54-92(1) requires the lowest floor, including a basement, and all mechanical and electrical equipment to be elevated at least one foot above the base flood elevation. Where the Red River Advisory Base Flood Elevation Map supersedes the FEMA map, § 54-92(6) raises that requirement to 18 inches above the advisory elevation instead.
Who has to certify the elevation of my new home?
A registered professional engineer, architect, or land surveyor must certify to the parish floodplain administrator that the lowest floor meets the § 54-92(1) standard, as part of the permit application information required under § 54-73(1)a. The parish keeps that certification on file.
Are commercial buildings held to the same elevation rule?
Nonresidential structures can meet the same one-foot freeboard, or instead be floodproofed watertight below that elevation under § 54-92(2), with structural components able to resist hydrostatic and hydrodynamic loads. An engineer or architect must certify the design and keep a record of the specific floodproofed elevation.
What is the penalty for not meeting the elevation standard?
Section 54-97 makes noncompliance with Chapter 54's flood damage prevention standards a misdemeanor, punishable by a fine of up to $100.00 or up to five days in jail, or both, with each day the violation continues treated as a new, separate offense.

Sources & Official References

Other rules in Bossier Parish

All Bossier Parish rules

Compare Bossier Parish to another location·View the Louisiana environmental rules overview

Get notified when Flood Elevation Requirements in Bossier Parish, LA changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.