Rochester Hills, MI Environmental Rules: Flood Elevation Requirements (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Residential freeboard
2 feet above base flood level
Nonresidential option
2-foot elevation or certified floodproofing
Elevation datum
NAVD88, Section 114-157
Manufactured homes
Prohibited in floodplain, Section 114-193
As-built certification
Required after construction, Section 114-160

Summary

Rochester Hills requires the lowest floor of a new or substantially improved residential structure in the floodplain to sit at least two feet above the base flood level under City Code Section 114-194(a)(1), a two-foot freeboard above the FEMA 100-year flood elevation. A floodplain use permit application must show that elevation, and every other elevation, measured against the North American Vertical Datum of 1988 under Section 114-157.

(a)Application for a floodplain use permit shall include the following:(1)A site plan showing existing structures, topographical features, and all proposed changes. The site plan shall include existing and proposed ground elevations and contours (one-foot intervals) and a contour showing the base flood elevation;(2)The elevation in relation to the North American Vertical Datum of 1988 (NAVD88) of the lowest floor of all structures; ... (1)Residential structures. The lowest floor of a residential structure shall be elevated at least two feet above the base flood level.

Full Breakdown

Chapter 114's floodplain standards division sets elevation requirements once a structure is allowed in or next to the floodplain. Section 114-194(a)(1) requires the lowest floor of a residential structure to be elevated at least two feet above the base flood level, the two-foot margin functioning as the city's freeboard above FEMA's one-percent-annual-chance flood elevation. A nonresidential structure gets a choice under Section 114-194(a)(2): the same two-foot elevation, or floodproofing to a watertight, substantially impermeable standard certified by a licensed professional engineer or architect as able to resist hydrostatic and hydrodynamic loads.

Fully enclosed areas below the lowest floor that could flood must equalize hydrostatic pressure automatically, meeting either an engineer's certification or the code's own minimum, a minimum of two openings totaling at least one square inch of net area per square foot of enclosed area, with the bottom of every opening no higher than one foot above grade. Before any of this is built, Section 114-157 requires the floodplain use permit application to show existing and proposed ground elevations and contours at one-foot intervals, a contour marking the base flood elevation, and the elevation of the lowest floor of every structure, all measured against the North American Vertical Datum of 1988 (NAVD88).

Once construction finishes, Section 114-160 requires the permit holder to give the engineering department a certified as-built elevation of the lowest floor, again referenced to NAVD88, certified by a licensed professional land surveyor or engineer licensed in Michigan. Manufactured homes are barred from the floodplain entirely under Section 114-193, regardless of elevation.

Violations & Fines

Article III has no elevation-specific fine, so building below the required two-foot freeboard, or without floodproofing certification for a nonresidential structure, falls under the citywide default penalty in Section 1-16: a misdemeanor punishable by up to 90 days in jail, a fine of up to $500.00, or both. Because Section 1-17 treats a continuing Code violation as a nuisance per se, the city can also seek an injunction against a structure built below the required elevation.

Frequently Asked Questions

How high above base flood level must a house be built in Rochester Hills?
The lowest floor of a residential structure in the Rochester Hills floodplain must be elevated at least two feet above the base flood level under Section 114-194(a)(1). The base flood is the flood having a one-percent chance of being equaled or exceeded in any given year, also called the 100-year flood, so the two feet functions as the city's freeboard above that FEMA-mapped elevation.
Can a commercial building be floodproofed instead of elevated?
A nonresidential structure can either meet the same two-foot elevation above base flood level or be floodproofed instead, under Section 114-194(a)(2). Floodproofing requires the structure, together with its utility and sanitary facilities, to be watertight below the base flood level with walls substantially impermeable to water, certified by a licensed professional engineer or architect as able to resist hydrostatic and hydrodynamic loads and buoyancy.
What datum does Rochester Hills use for flood elevations?
Elevations in a Rochester Hills floodplain use permit application are measured against the North American Vertical Datum of 1988 (NAVD88) under Section 114-157. The application must show the elevation of the lowest floor of every proposed structure, a contour marking the base flood elevation, and, after construction, a certified as-built lowest-floor elevation submitted to the engineering department under Section 114-160.

Sources & Official References

Other rules in Rochester Hills

All Rochester Hills rules

Compare Rochester Hills to another location·View the Michigan environmental rules overview

Get notified when Flood Elevation Requirements in Rochester Hills, MI changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Flood Elevation Requirements in Nearby Cities

How other cities in Oakland County handle flood elevation requirements.

Farmington Hills, MI
Some Restrictions