Wicomico County, MD Environmental Rules: Flood Elevation Requirements (2026)

Significant Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Flood protection elevation
BFE plus 2 feet of freeboard
Residential lowest-floor rule
at or above flood protection elevation
Electric panelboard height
at least 3 feet above BFE
Zone AO alternate rule
FIRM depth number plus 2 feet, min. 4 feet
Critical facility elevation
flood protection elevation plus 1 foot
Proof required
signed elevation certificate from licensed surveyor/engineer

Summary

Wicomico County defines the flood protection elevation as the base flood elevation plus two feet of freeboard, requires new and substantially improved residential lowest floors to reach that height, and makes electric panelboards sit at least three feet above the BFE.

These county ordinances apply to unincorporated areas of Wicomico County. Incorporated cities within the county may have their own rules that take precedence over county-level regulations.

FLOOD PROTECTION ELEVATION The base flood elevation plus two feet of freeboard. ... F. Have the electric panelboard elevated at least three feet above the BFE. ... (1) Lowest floors shall be elevated to or above the flood protection elevation.

Full Breakdown

Under Wicomico County Code § 149-10, 'flood protection elevation' means the base flood elevation plus two feet of freeboard, the safety margin that compensates for uncertainty from wave action, obstructed bridge openings, debris and ice jams, climate change and watershed urbanization. That definition drives § 149-34A(1), which requires new residential structures, residential portions of mixed-use structures, and substantially improved existing residential structures to have their lowest floors elevated to or above the flood protection elevation; in Zone AO shallow-flooding areas, the lowest floor instead must sit at least as high above the highest adjacent grade as the FIRM's depth number plus two feet, or four feet if no depth number is shown (§ 149-34A(2)).

Beyond the floor itself, § 149-22 requires electrical systems, HVAC and plumbing equipment to sit at or above that same elevated lowest floor, or, as an alternative, to be designed and installed to resist flood forces and keep water out if placed lower (§ 149-22D, E). Section 149-22F adds a specific mandate that the electric panelboard be elevated at least three feet above the base flood elevation, a stricter number than the two-foot general freeboard. Critical and essential facilities such as hospitals and fire stations face an even higher bar: they must be elevated to the greater of the flood protection elevation plus one foot, the building code elevation, or the five-hundred-year flood elevation, and may not be sited in coastal high-hazard areas, Coastal A Zones or floodways at all (§ 149-27).

Violations & Fines

Building below the required flood protection elevation or panelboard height is enforced the same way as any other Chapter 149 violation: it is presumed a violation until required documentation such as an elevation certificate is provided (§ 149-10, definition of VIOLATION), and under § 149-50A a person who fails to meet permit conditions, including elevation requirements, is guilty of a misdemeanor punishable by a fine of $100 to $1,000, up to 30 days imprisonment, or both, with each day of continued violation a separate offense. The Floodplain Administrator may also issue a stop-work order under § 149-49 until the elevation deficiency is corrected.

Frequently Asked Questions

How high above the base flood elevation must a new house be built in Wicomico County?
Section 149-34A(1) requires the lowest floor to reach the 'flood protection elevation,' which § 149-10 defines as the base flood elevation plus two feet of freeboard.
Where must the electric panelboard sit relative to the flood elevation?
Section 149-22F specifically requires the electric panelboard to be elevated at least three feet above the base flood elevation, a stricter standard than the general two-foot freeboard.
Is there a different elevation rule for Zone AO shallow flooding areas?
Yes. Section 149-34A(2) requires the lowest floor there to sit at least as high above the highest adjacent grade as the FIRM's stated depth number plus two feet, or at least four feet if no depth number is specified.
What proof does the county require that a building meets the elevation rule?
Applicants sign an agreement to submit an elevation certificate prepared by a licensed professional engineer or surveyor, filed once the lowest floor is placed and again before the certificate of occupancy issues, per the definitions in § 149-10.

Sources & Official References

Other rules in Wicomico County

All Wicomico County rules

Compare Wicomico County to another location·View the Maryland environmental rules overview

Get notified when Flood Elevation Requirements in Wicomico County, MD changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.